[49]
Figure 31.
List AC: -48V Distribution Panel (with Return Busbar) and
List AD: -48V Distribution Panel (without Return Busbar),
(4) GJ/218 Circuit Breaker Positions
Figure 32.
List AE: -48V Distribution Panel,
(2) TPH Fuse Positions (without Shunts) (without Return Busbar)
-48VDC Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.375 inches.
Return Busbar
(not included with List AD)
Observe proper
polarity when making
load connections.
WARNING!
For an 800A circuit breaker,
load must not exceed 600A.
-48VDC Load
Connections
LOAD CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.88 inches.
Observe proper
polarity when making
load connections.
WARNING!
For an 800A fuse,
load must not exceed 600A.