NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[54]
Figure 40.
List DC: -48V/+24V Distribution Panel,
(9) –48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and
(12) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)
Figure 41.
List DD: -48V/+24V Distribution Panel,
(5) –48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and
(16) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)
Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
-48V Distrib
ution
+24V Distr
ibution
Observe proper
polarity when making
load connections.
WARNING!
Caution: A circuit breaker or fuse with a rating
of 100A or greater SHALL HAVE an empty
mounting position between it and any
other overcurrent protective device.
Load
Connections
-48V
Distribution
+24V Distr
ibution
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
Observe proper
polarity when making
load connections.
WARNING!
Caution: A circuit breaker or fuse with a rating
of 100A or greater SHALL HAVE an empty
mounting position between it and any
other overcurrent protective device.