NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[55]
Load Connections to Return Bar
Figure 42.
List GA: Return Bar Panel
Load Connections to GMT Distribution Fuse Block
Figure 43.
Optional Bullet Nose 6-Position GMT Distribution Fuse Block
Load and/or Battery
Return Connections
LOAD AND/OR BATTERY RETURN CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.38 inches.
Load Return Leads
-48VDC Load Leads
Wire Size Capacity: 26-14 AWG.
Recommended Torque: 4.5 in-lbs.
35A maximum capacity per block.
Maximum GMT fuse size is 15A.