NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[60]
Battery Connections to Distribution Cabinet Battery Busbars
WARNING!
Observe proper polarity when making battery connections.
Battery may be connected to the battery busbars located in the distribution cabinet, depending on site requirements. See
Figure 50.
Battery Connections to Distribution Cabinet Battery Busbars
(4-Row Cabinet Shown,
Others Similar)
Battery
(Return Side)
Busbar
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
Battery
(Load Side)
Busbar
GND RTN
-48V SUPPLY
BATTERY AND BATTERY RETURN CONNECTIONS
(7 landings per polarity)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
additional hardware)
Maximum Lug Width: 1.88 inches
(unless otherwise noted).
Maximum Lug Width: 1.25 inches
(this location only).
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
BATTERY AND
BATTERY RETURN CONNECTIONS
(4 landings per polarity)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
additional hardware)
BATTERY AND
BATTERY RETURN CONNECTIONS
(4 landings per polarity)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
additional hardware)
1-Row Cabinet
2-Row Cabinet
3-Row and 4-Row Cabinets
Central Office
Ground
Central Office
Ground
Central Office
Ground
Warning