NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[65]
Installing the Rectifier and Converter Modules into
Spec. No. 588705300 Module Mounting Shelves
Rectifier and converter modules can be inserted or removed with power applied (hot swappable).
Rectifiers modules can be installed in any mounting position of each module mounting shelf. Converters modules can be installed in any
of the three far right mounting positions of each module mounting shelf. See
Note:
Each rectifier and converter module locks into the module mounting shelf by means of a latch located on the bottom of the module. The
latch and module handle are interactive. Pushing the handle up into the module’s front panel causes the latch to extend to the locking
position; pulling the handle down out from the module’s front panel causes the latch to retract. See
WARNING!
To prevent damage to the latching mechanism, ensure the handle is in the open position when installing or
removing a module. NEVER hold the handle in the closed position when installing a module into a shelf.
PROCEDURE
1.
Unpack the modules.
2.
Note the model number located on the front of each module. Model numbers starting with the letter “R” are rectifier modules.
Model numbers starting with the letter “C” are converter modules.
3.
Place the module into an unoccupied mounting position without sliding it in completely. Rectifiers modules can be installed in
any mounting position of each module mounting shelf. Converters modules can be installed in any of the three far right
mounting positions of each module mounting shelf. See
4.
Loosen the captive screw on the module’s handle. Pull the handle down out from the module’s front panel (this will also retract
the latch mechanism). See
5.
Push the module completely into the shelf.
6.
Push the handle up into the module’s front panel. This will lock the module securely to the shelf. Tighten the captive screw on
the handle.
7.
Repeat the above steps for each module being installed in the system.
8.
After the modules are physically installed in the mounting shelf(s), they are ready for operation immediately after power is
supplied to them.
Warning