NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[68]
submenu will be indicated by the cursor. Press ENT to
open the submenu.
Note:
Repeatedly press the “ESC” key to return in reverse
order level by level from any submenu until the Main
screen appears.
8.
Verify and set the ACU+ controller as required for your
application. Refer to the ACU+ Instructions
(UM1M820BNA or UM1M820DNA400) for procedures.
Note that you will have to program the ACU+ for any
temperature probes and external inputs/outputs
connected to the IB2 Interface Board, optional EIB
Interface Board, and optional SM-DU+ Shunt Interface
Board.
Verifying the Configuration File
Your ACU+ was programmed with a configuration file that sets all
adjustable parameters. The version number of the configuration
file can be found on the configuration drawing (C-drawing) that is
supplied with your power system documentation, and on a label
located on the ACU+. You can verify that the correct configuration
file has been loaded into your ACU+ by performing the following
procedure.
Note:
The quantity of LVD’s and shunt values for your specific system
may be different from the values shown on the C-drawing.
PROCEDURE
Note:
When viewing any of the following screens, if a key is not
depressed within approximately 10 seconds, the ACU+ will
automatically return to the Main screen.
1.
With the Main screen displayed, press ESC. A screen
displays the serial number and software version.
2.
Press ENT. A screen displays the hardware version and
MAC address.
3.
Press ENT. A screen displays the configuration version
number.
4.
Press ESC, or wait approximately 10 seconds, to return to
the Main screen.
Checking Basic System Settings
Navigate through the controller menus and submenus to check
system settings. You can adjust any parameter as required. Note
that these settings can also be checked (and changed if required)
via the WEB Interface.
Note:
Repeatedly press the “ESC” key to return in reverse order level
by level from any submenu until the Main screen appears.
PROCEDURE
1.
To Select a Sub-Menu:
Press the up or down arrow keys to move the cursor up
and down the list of sub-menus in the menu screen
(selects the sub-menu), then press ENT to enter the
selected sub-menu.
2.
To Enter a Password:
If a password screen opens, a password must be entered
to allow the User to make adjustments. To enter a
password, with the cursor at the User Name field (default
is “Admin”), press the down arrow key to move cursor
down to the password line. Press ENT. “0” is highlighted.
Press the up arrow key once to change the “0” to”1”
(default password is “1”), then press ENT twice. (
Note:
If
you have been assigned a unique User Name and password,
follow this procedure to enter these.)
3.
To Change a Parameter:
Press the up or down arrow keys to move the cursor up
and down the list of parameters in the menu screen
(selects the parameter to change), then press ENT to
change the selected parameter. The parameter field
highlights. Press the up or down arrow keys to change
the parameter value. Press ENT to confirm the change.
4.
shows the menu navigation for some basic
settings. Refer to the separate ACU+ Manual
(UM1M820BNA or UM1M820DNA400) supplied with
your power system for complete Local Display menus.