NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[71]
5.
Navigate to and select “Set Conv ID”. Press ENT. Use the
up or down keys to change the ACU+ identification
number for the flashing converter. Press ENT.
6.
Press ESC to return to converter menu screen.
7.
Navigate to and select the next converter.
8.
Repeat steps 4) through 7) for each of the remaining
converters in the system.
9.
When you have finished selecting identification numbers
for all converters, repeatedly press ESC to return to the
Main Menu.
10.
Navigate to and select “Manual” (ENT) / “Converter”
(ENT) / “All Conv Ctrl” (ENT).
11.
Navigate to “Confirm ID”. Press ENT. “Yes” highlights.
12.
Press ENT to select the operation. Press ENT again to
confirm.
Note:
Check you numbering to be sure it is correct. If there
where conflicts in your numbering, converters with
conflicts will be assigned the next available sequential
number.
13.
Return to the Main screen by repeatedly pressing ESC
(escape).
ACU+ Alarm Relay Check
To verify operation of the external alarm relays, use the ACU+
alarm relay test feature. Refer to the ACU+ Instructions
(UM1M820BNA or UM1M820DNA400) for instructions in using
this feature.
Note:
The relays may be preprogrammed for specific functions.
Refer to the configuration drawing (C-drawing) supplied with
your system for your system’s specific configuration.