NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[69]
Table 8.
ACU+ Basic Settings Menu Navigation
Parameter
Menu Navigation
Date
Main Menu / Settings / Controller / Date
Time
Main Menu / Settings / Controller / Time
IP Communications Parameters
(IP address, subnet mask address,
gateway address)
Main Menu / Settings / Communication
Float Voltage
Main Menu / Settings / Battery / Charge / Float Voltage
Equalize Voltage
Main Menu / Settings / Battery / Charge / EQ Voltage
Battery Capacity
Main Menu / Settings / Battery / Battery 1 / Rated Capacity
BTRM Feature
Main Menu / Settings / Battery / Basic / BTRM Action
Main Menu / Settings / Battery / Basic / BTRM Voltage
Temperature Compensation
Center Temperature
Main Menu / Settings / Battery / Temp Comp / Temp CompCenter
Temperature Compensation Slope Main Menu / Settings / Battery / Temp Comp / Temp Comp Coeff
Temperature Compensation Sensor Main Menu / Settings / Battery / Temp Comp / TempComp Sensor
Temperature Compensation
Maximum Voltage
Main Menu / Settings / Battery / Temp Comp / Temp Comp Max V
Temperature Compensation
Minimum Voltage
Main Menu / Settings / Battery / Temp Comp / Temp Comp Min V
HVSD Limit
Main Menu / Settings / Rectifier / All Rect Set / HVSD Limit
Rectifier Current Limit
Main Menu / Settings / Rectifier / All Rect Set / Curr Limit Pt
Over Voltage Alarm 1
Main Menu / Settings / Power System / General / Over Voltage 1
Over Voltage Alarm 2
Main Menu / Settings / Power System / General / Over Voltage 2
Under Voltage Alarm 1
Main Menu / Settings / Power System / General / Under Voltage 1
Under Voltage Alarm 2
Main Menu / Settings / Power System / General / Under Voltage 2
Changing Battery Capacity Rating in the ACU+
To change the battery capacity setting of the ACU+ to match the
battery connected to the power system, perform the following
procedure.
PROCEDURE
1.
With the Main screen displayed, press ENT to go to the
Main Menu. Navigate to and select “Settings” (ENT).
2.
If a password screen opens, a password must be entered
to allow the User to make adjustments. If a password was
previously entered and has not yet timed out, skip this
step and proceed to step 3). Otherwise, to enter a
password, with the cursor at the User Name field (default
is “Admin”), press the down arrow key to move cursor
down to the password line. Press ENT. “0” is highlighted.
Press the up arrow key once to change the “0” to”1”
(default password is “1”), then press ENT twice. (
Note:
If
you have been assigned a unique User Name and password,
follow this procedure to enter these.)
3.
With the Settings menu screen displayed, navigate to
and select “Battery” (ENT) / “Battery 1” (ENT).
4.
Navigate to “Rated Capacity”. Press ENT. Use the up or
down keys to adjust the value as required. Press ENT.
5.
Return to the Main screen by repeatedly pressing ESC
(escape).
Configuring the ACU+ Identification of Rectifiers and Assigning
which Input Phase is Connected to the Rectifiers
When rectifiers are all installed prior to applying power and
starting the system, the order in which the ACU+ identifies the
rectifiers is by serial number (lowest serial number is Rect 1, next
lowest is Rect 2, etc.). If you prefer the ACU+ to identify the