Chapter 5 Use Of Monitoring Module M800D 37
5.2 Use Of The Operation Panel
The first screen is the language-selecting screen, as shown in the following figure. User can select English or other
language in the screen by pressing ▲ and ▼, and press ENT to enter the main screen after selecting the language. If
no key has been pressed for 30 seconds, user will enter the main screen directly.
英语
English
5.2.1 Main Screen
The main screen is shown in the following figure.
2005-06-30
53.5V
7.8A
System:
Alarm
Float Charge
The main screen displays system time, DC voltage, DC current, system status and battery status. The system time
displays the date and time alternatively.
In the default main screen:
Press ◄ or ► to change the contrast of LCD
Press ▲ and ▼ and ESC together to log out (The password will be invalid)
Press ENT and ESC together to reset M800D
Press ENT to enter main menu
5.2.2 Main Menu
The main menu is the highest- level menu. The setting, controlling, information querying (rectifier information and
alarm information) of all the parameters are carried out by the submenus of the main menu. The main menu is shown
in the following figure.
Main Menu
Running Info
Maintain
Parameter Set
1. Press ENT in any screen of the main screen to enter main menu.
2. Press ESC in the submenu to return to the main screen step by step.
5.2.3 Running Information
1. Introduction to running info
In the screen of Main Menu, press ▲ or ▼ to select the sub-menu of “Running Info”, and press ENT to activate the
menu to show the screen of “Running Info”:
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual