Chapter 6 Use Of Monitoring Module M501D 83
1. The LCD will prompt you to select a language once the monitoring module is powered on.
English
You can use ◄, ►, ▲ or ▼ to select the language you want, and press ENT to confirm. If the user does not press
any key for 10 seconds, the monitoring module will select automatically the current language.
2. The monitoring module will prompt you to wait, and start initialization.
Waiting...
3. The first system information page appears
2005-06-30
53.5V
Alarm
Auto Float
500A
The system information is shown in many pages. You can repeatedly press ▼ to view other system information
pages in a cycle.
4. Press the ESC key at the information root screen, and the user can browse the serial number of the module, the
software version and the operation time of the module.
Serial No: 202311
3920204C000112
SW Rev: 1.13
Runtime: 140h
5. At any system information page, press ENT to enter the ‘MAIN MENU’ page, which contains 3 sub-menus: ‘Status’,
‘Maintenance’ and ‘Settings’.
Main Menu
Status
Maintenance
Settings
You can press ▲ or ▼ repeatedly to select a sub-menu, and press ENT to enter the sub-menu. Press ESC to return
to the menu of higher level.
Status
Including rectifier information, active alarm information and alarm history information.
1) Maintenance
The maintenance operation can be conducted only when the battery management mode is set to ‘Manual’. The
maintenance includes battery FC, BC and test, load power off/on, battery power off/on and rectifier voltage trimming,
current limit, switch control and resetting.
2) Settings
Including the setting of alarm parameter, battery parameter, AC/DC parameter, rectifier parameter and system
parameter.
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual