34 Chapter 4 Use Of Monitoring Module M500D
5. The model description is shown below:
48V /30A /300 /MAN
AC input switchover:
AUTO/MAN/NONE
System shunt coefficient:
100/300/500/SET
Rectifier rated output current:
15A/30A/50A/75A/100A
Rectifier rated output
voltage: 48V/24V
8.
Note
Monitoring module M500D can monitor multiple power systems made by Emerson. If the system type is not set correctly,
unpredictable faults may occur.
4.7.11 Alarm Settings
1. The first page of the setting interface is show below:
ALARM SETTINGS
Alarm Type
Alarm Mode
Alarm Control
There are 3 submenus. Use “▼” or “▲” to select one, and use “ENT” to confirm.
2. The three submenus are shown below:
Alarm Type:
Alarm Block
Level: Major
Relate Relay: 1
Alarm Mode:
DI No: 1#
Mode: HIGH
Set DI Name: 2#
Clear Hist Alarm:
N
Block Alarm:
N
Use “▼” or “▲” to select one page or one of the parameters, and “◄” or “►” to select the parameter value. Press
“ENT” to confirm and save.
3. After setting the “Set DI Name” and confirming it, the system will prompt you to name the DI:
DI
Name
:
SPD
Use “▼” or “▲” to change the number, and “◄” or “►” to move the cursor left or right. Press “ENT” to confirm.
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual