background image

NetSure

 -48 VDC Power System 

User Manual, UM582137200 

Spec. No: 582137200 

 

Document Code:  UM582137200 

Model No: NetSure™ 5100 

 

Revision A, January 11, 2017 

[1 of 17]

 

Customer Documentation Package 

This document (UM582137200) provides 

User Instructions

 for 

-48 VDC Power System Model NetSure™ 5100, Spec. No. 
582137200. 

The complete Customer Documentation Package consists of… 

NetSure

 -48 VDC Power System Installation Manual 

 

Power System Installation Instructions: IM582137200 

NetSure

 NCU Controller User Manual 

 

NCU Controller User Instructions: UM1M830BNA 

USB Drive with All Customer Documentation 

 

Power System Installation Instructions: IM582137200 

 

Power System User Instructions: UM582137200 

 

Power System “System Application Guide”: 
SAG582137200 

 

NCU Controller User Instructions: UM1M830BNA 

 

Rectifier Instructions: UM1R482000e3 

 

Engineering Drawings 

 

Also provided on the USB drive is a Controller 
Configuration Drawing (C-drawing) and the controller 
configuration files loaded into the controller as shipped. 

For factory settings of all configurable controller parameters, refer 
to the Configuration Drawing (C-drawing) supplied with your 
power system. 

System Description 

-48 VDC @ up to 150 Amperes Power System 

The NetSure™ 5100 DC Power System is an integrated power 
system containing rectifiers, intelligent control, metering, 
monitoring, and distribution. 

This power system is designed to power a load while charging a 
positive grounded battery.  This power system is capable of 
operating in a batteryless installation or off battery for 
maintenance purposes.  The power system is designed for 
operation with the positive output grounded. 

The NetSure 5100 consists of the following components mounted 
in a 19” or 23” wide relay rack or cabinet rack.  Wall mounting 
options are also available. 

Controller 

NCU (NetSure Control Unit):  The controller provides power system 
control (including optional low voltage battery disconnect [LVBD] 
and low voltage load disconnect [LVLD] control), rectifier control 
(including a charge control function), metering functions, 
monitoring functions, local/remote alarm functions, and 
connections for binary inputs and programmable relay outputs via 
a controller interface board.  The controller also supports rectifier 
temperature compensation if the system is equipped with a 
temperature probe(s).  Temperature probe(s) may also be 
designated to monitor ambient temperature and/or battery 
temperature.  The controller also provides data acquisition, system 
alarm management, and advanced battery and energy 
management.  The controller contains a color TFT display and 
keypad for local access.  The controller provides an Ethernet port 
and comes with comprehensive webpages for remote access.  The 
controller has 

optional 

SNMP v3 capability for remote system 

management.  The controller supports software upgrade via its 
USB port.  Refer to the NCU Controller Instructions 
(UM1M830BNA) for more information. 

Rectifier Modules 

The system contains rectifier modules, which provide load power, 
battery float current, and battery recharge current during normal 
operating conditions.  Refer to the Rectifier Instructions 
(UM1R482000e3) for more information. 

Distribution Unit 

Various distribution unit options are available.  See 
SAG582137200 for descriptions.  The distribution unit can be 
equipped with an optional Low Voltage Battery Disconnect (LVBD) 
or Low Voltage Load Disconnect (LVLD) contactor.  The 
distribution unit provides DC distribution through circuit breakers 
and/or fuses. 

Operating Procedures 

Controller and Rectifier 

For operation instructions on these units, refer to the following 
documents. 

 

NCU Controller Instructions (UM1M830BNA) 

 

NOTE:   The controller’s default “User Name” is "admin" 
and the default “Password” is “640275”. 

 

Rectifier Instructions (UM1R482000e3) 

Summary of Contents for NetSure 5100

Page 1: ...NetSure 48 VDC Power System User Manual UM582137200 Revision A January 11 2017 Specification Number 582137200 Model Number NetSure 5100 ...

Page 2: ...NetSure 48 VDC Power System User Manual UM582137200 Spec No 582137200 Document Code UM582137200 Model No NetSure 5100 Revision A January 11 2017 This page is intentionally blank ...

Page 3: ...r Documentation Package 1 System Description 1 Operating Procedures 1 Controller and Rectifier 1 ESTOP Function 2 Controller Battery Charge Current Limit Feature 2 Local Controls and Indicators 2 Maintenance 2 System Maintenance Procedures 2 Adding a Rectifier 2 Installing a Field Expansion Rectifier Shelf 2 Troubleshooting and Repair 8 Contact Information 8 Controller and Rectifier 8 Controller C...

Page 4: ...ury if not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts the reader to an action that must be avoided in order to protect equipment software data or service ISO ALERT Alerts the reader to an action that must be performed in order to preven...

Page 5: ...t breakers remain de energized during installation DO NOT apply AC input power to the system until all electrical connections have been completed and checked DC Output and Battery Voltages DANGER This system produces DC power and may have a battery source connected to it Although the DC voltage is not hazardously high the rectifiers and or battery can deliver large amounts of current Exercise extr...

Page 6: ...atteries Do not dispose of batteries in a fire They may explode ALWAYS FOLLOW THE BATTERY MANUFACTURER S RECOMMENDATIONS AND SAFETY INSTRUCTIONS DANGER This equipment may be used in conjunction with lead acid batteries Working near lead acid batteries is dangerous In addition to the hazard of electric shock gas produced by batteries can be explosive and sulfuric acid can cause severe burns Do not ...

Page 7: ...NFPA 70E Standard for Electrical Safety in the Workplace Hazardous Voltage DANGER Hazard of electrical shock More than one disconnect may be required to de energize the system before servicing Handling Equipment Containing Static Sensitive Components ALERT Installation or removal of equipment containing static sensitive components requires careful handling Before handling any equipment containing ...

Page 8: ...in one megohm resistor no external resistor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Handle equipment containing static sensitive components only by the edges that do not have connector pads 4 After removing equipment containing static sensitiv...

Page 9: ...ntroller NCU NetSure Control Unit The controller provides power system control including optional low voltage battery disconnect LVBD and low voltage load disconnect LVLD control rectifier control including a charge control function metering functions monitoring functions local remote alarm functions and connections for binary inputs and programmable relay outputs via a controller interface board ...

Page 10: ...g as battery voltage is above 47 VDC Local Controls and Indicators Controller and Rectifier Refer to the controller and rectifier instructions for descriptions of the local controls and indicators located on these units Maintenance System Maintenance Procedures It is recommended to perform the maintenance procedures listed in Table 1 every 6 months to ensure continual system operation Table 1 Main...

Page 11: ...hese busbars to the expansion module mounting assembly with the hardware provided with the expansion module mounting assembly Secure these busbars to the main module mounting assembly with the hardware provided with the main module mounting assembly Refer to Figure 1 for hardware build up and torque 8 Disconnect the cable coming from the distribution unit that is connected to the left side as view...

Page 12: ...rear shield from the expansion module mounting assembly MOUNTING HARDWARE 12 24 x 3 4 Thread Forming Hex Head Screw No 10 12 Ground Washer Torque 65 in lbs Install the ground washers so the teeth make contact with the metal on the mounting angles 23 Front AC Option Shown 19 Rear AC Option Similar Rear Shield Rear Shield Rear Rear Front 2 When the main module mounting assembly is configured with th...

Page 13: ... Build Up Busbar M6 Flat Washer M6 Lock Washer M6 Hex Nut Torque to 52 in lbs Hardware Build Up Busbar M6 Flat Washer M6 Lock Washer M6 Hex Nut Torque to 52 in lbs 5 Install the busbars provided with the expansion module mounting assembly between the shelves Torque to52 in lbs Do this by removing the hardware from the main shelf busbars loosening the hardware on the expansion shelf busbars and sli...

Page 14: ...ry 11 2017 6 of 17 Figure 1 Installing a Field Expansion Rectifier Shelf cont d from previous page Rear Installed View 6 Install the new rear shields supplied with the expansion module mounting assembly to the main module mounting assembly 7 Re install the rear shield previously removed onto the expansion module mounting assembly Rear ...

Page 15: ...t List 01 Main Shelf List 02 Expansion Shelf Cable P N 555716 Provided with Expansion Shelf Field Installed Exploded View Shown to Illustrate Wire Connections Only Termination Resistor P N 548398 Termination Resistor P N RPM628350 2 Distribution Unit with List 01 Distribution Unit with List 01 and 02 Termination Resistor P N 548398 These Are Factory Connected Together These Are Factory Connected T...

Page 16: ...ded the new current limit setpoint will be 100 of the combined capacity including the new rectifier module If a rectifier module is removed from the system and the Rect Comm Fail is cleared the current limit point will remain unchanged unless the capacity of the remaining rectifiers is not sufficient to maintain this current limit point If that happens the current limit point will automatically de...

Page 17: ...LACING THE NCU CONTROLLER Refer to the NCU Controller Instructions UM1M830BNA for a controller replacement procedure REPLACING A DISTRIBUTION DEVICE Replace distribution devices with the same type and rating Refer to System Application Guide SAG582137200 for part numbers Replacing a GMT Distribution Fuse Procedure 1 Refer to Figure 3 and replace the fuse Ensure a safety fuse cover is installed on ...

Page 18: ...l No NetSure 5100 Revision A January 11 2017 10 of 17 Figure 3 GMT Distribution Fuse Replacement List BA BC BF LC NA NC NF Figure 4 Installation of Safety Fuse Covers GMT Fuse Safety Cover Front List BA shown List BC BF LC NA NC NF similar Safety Cover P N 248898700 GMT X Safety Cover P N 102774 GMT Y ...

Page 19: ...ockets on distribution unit Insert these terminals into corresponding sockets on distribution unit Shorter Side of Breaker Longer Side of Breaker Longer Side of Breaker Turn circuit breaker off before installing OFF Position Towards Center List BC shown List LC NC similar Load Disconnect Circuit Breakers Front Components removed in illustration for clarity only Load Distribution Circuit Breakers I...

Page 20: ...mper and Switch Options section of the Power System Installation Instructions IM582137200 8 Orient the replacement circuit card over its mounting position and secure with the screws removed from the old circuit card 9 Plug all connectors removed from the old circuit card into the same position on the replacement circuit card 10 Reinstall the rear top cover to the distribution unit 11 Remove the gr...

Page 21: ...riate personnel that this procedure is finished 16 Ensure that there are no local or remote alarms active on the system Replacing the IB4 Board if furnished Procedure NOTE Refer to Figure 9 as this procedure is performed 1 Performing this procedure may activate external alarms Do one of the following If possible disable these alarms If these alarms cannot be easily disabled notify the appropriate ...

Page 22: ...ard Rear Rear The IB2 Controller Interface Board OR The IB4 Second Controller Ethernet Port Board Can Be Installed in the Distribution Unit Slide Out Tray with IB2 Board Installed Slide Out Tray with IB4 Board Installed System Interface Board 10M Ethernet Port RJ 45 LAN Connection 10M Ethernet Port RJ 45 LAN Connection USB B Port Factory connected to NCU Controller backplane USB B Port Customer co...

Page 23: ... or system is not connected here System Interface Board 1 2 3 No Battery Pwr Battery Pwr Shorting Jumper J4 Selects to power controller from Battery Power or not if a battery LVD contactor is furnished J4 1 2 3 System Temp 1 System Temp 2 CAN Port RJ 45 H1 J1 J2 J3 J4 J7 J8 R1 R2 R3 1 1 1 1 BATT PW R 562209 0 0 0 X X X X X A X X X X X X X X System Interface Board P N 562209 J3 Wire Size Capacity 1...

Page 24: ...4 2 8 7 6 5 4 3 2 1 NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 Relay No Relay No Input No Input No 8 7 6 5 4 3 2 1 ON OFF 1 2 Rear The IB2 Controller Interface Board OR The IB4 Second Controller Ethernet Port Board Can Be Installed in the Distribution Unit Slide Out Tray with IB2 Board Installe...

Page 25: ... power systems and outside plant enclosures for customers and channel partners Reps VARs Distributors Phone 1 800 800 1280 option 2 Spare Parts Email DCpower Spares Emerson com OSP Spares Emerson com Pricing and purchase orders for spare parts including but not limited to breakers cables fuses rectifier fans misc breaker and fuse panels enclosure fans doors and switches etc Phone 1 800 800 1280 op...

Page 26: ...on Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Names of companies and products are trademarks or registered trademarks of the respective companies Any questions regarding usage of trademark names should be directed to the original manufacturer Emers...

Reviews: