SAG582127000
System Application Guide
Issue AF, February 26, 2014
Spec. No. 582127000 (Model 721
NPBB
)
Page 44 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List BF: Battery Disconnect Distribution Panel,
(2) TPH Fuse Battery Disconnect Positions (with Shunts) (without Return Busbar)
Features
♦
(2) -48V Battery Disconnect Fuse Mounting Positions:
70A to 800A TPH Type Fuses.
♦
Includes Shunts, 800A / 25mV. Each shunt is equipped with 10’ jumpers for connection to monitoring
device. If the system is equipped with an SM-DU+, the leads are trimmed and connected to the SM-DU+
(internal to the distribution cabinet).
♦
Does NOT include a Return Busbar.
♦
1200A Maximum Capacity.
Restrictions
Cannot be used with List 21.
Must be installed in top row only (limit one battery disconnect panel per distribution cabinet).
Maximum lug width, 1.88 inches.
For an 800A fuse, load must not exceed 600A.
Ordering Notes
1) Order fuses as required per
. Order replacement alarm fuses (1/4A) per
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16
hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
Battery
Connections
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
Maximum Lug Width: 1.88 inches.
(Customer must supply
or order additional
hardware)