Battery Busbar Extension Kit (P/N 554541)
Features
♦
Provides busbar extension plates and mounting hardware for extending battery
busbars through the top of a distribution cabinet. Each busbar extension plate
provides three pairs of clearance holes for 3/8” hardware on 1” centers. Allows
back-to-back lug landing for up to six lugs per polarity. See "Battery Input
Illustrations" on page 104.
Ordering Notes
1) Order one (1) kit P/N 554541 per bay, as required.
Battery Landing Busbar Kit (P/N 553584)
Features
♦
Provides a Battery Landing Busbar Kit that attaches to the distribution cabinet’s
battery busbars and hangs off the back of the cabinet. Six (6) battery landing
positions are provided (per polarity) (1/4-20 x 0.875” studs on 0.625” centers).
See "Battery Input Illustrations" on page 104.
Restrictions
For use with List 21.
CANNOT be used with List 2 or List 3.
Ordering Notes
1) Order one (1) kit P/N 553584 per bay, as required.
Battery Landing Busbar Kit (P/N 555478)
Features
♦
Provides a Battery Landing Busbar Kit that attaches to the distribution
cabinet’s battery busbars and hangs off the back of the cabinet. Four (4)
battery landing positions are provided (per polarity) for connection of up
to eight (8) battery leads (back-to-back) (per polarity) (1/4-20 x 0.875”
studs on 0.625” centers). See "Battery Input Illustrations" on page 104.
Restrictions
For use with Lists 22, 23, and 24.
CANNOT be used with List 2 or List 3.
Ordering Notes
1) Order one (1) kit P/N 555478 per bay, as required.