DC INPUT TO LIST 46 DC INPUT TERMINATION ASSEMBLY
(400 Volts DC)
Provides “1 DC Feed per 2 Converters” Input Terminations
(System with Spec. No. 58870500040 Converter Shelves)
Input
Voltage
Input
Current
Overcurrent
Protection
40°C Ambient
Temperature
Wire
(1) (2) (3) (5)
Conduit
Size
400V DC
22A
30A
10 AWG
1/2”
(4)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at
90°C conductor temperature. For operation in countries where the NEC is not recognized, follow applicable
codes.
2
Equipment grounding conductors must be provided with the DC input conductors supplied to the shelf.
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If
aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor
size. For operation in countries where the NEC is not recognized, follow applicable codes.
3
THHN 90
°
C Wire.
4
System with Four (4) Spec. No. 588705000 Converter Shelves: Conduit sized for four (4) current carrying
conductors and one (1) ground conductor per conduit (based on NEC recommendations), for four (4) converters.
For operation in countries where the NEC is not recognized, follow applicable codes.
5
Maximum loop length is 100 meters (328 feet). Loop length is the sum of the lengths of the positive and
negative leads.
Table 25
Recommended DC Input Branch Circuit Protection and Wire Size when Using
List 46 “1 DC Feed per 2 Converters” DC Input Termination Assembly,
System with Spec. No. 588705000 Converter Shelves