SAG582127000
System Application Guide
Issue AF, February 26, 2014
Spec. No. 582127000 (Model 721
NPBB
)
Page 26 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Restrictions
For use with 58870500040 module mounting shelf only.
Factory installed only.
For initial installation only. Initial module mounting shelves are factory wired to List 47. If a field expansion
module mounting shelf is added to the system, DC inputs MUST be wired directly to the shelf.
Ordering Notes
1) Order either List 45, 46, or 47 for each bay (or order module mounting shelves with DC input terminal
blocks). See PD588705000.
List 60: Converter Interface Components (for Spec. No. 588705300)
Features
♦
Provides components to interface
converters in Spec. No. 588705300
module mounting shelves to the
distribution cabinet.
Restrictions
Must be used in systems equipped with
Spec. No. 588705300 module mounting
shelves.
Must be installed in main bay
only
.
Must be used in conjunction with a dual
voltage bus distribution panel.
Ordering Notes
1) Order List 60 as required. Quantity of List 60 must equal the quantity of module mounting shelf(s) Spec.
No. 588705300 installed in the bay with a maximum of four (4) List 60. Note that if five (5) shelves are in
the bay, the quantity of List 60 is still four (4).
2) Specify the number of module mounting shelf(s) Spec. No. 588705300 installed in the bay (one to five) so
correct busbars can be provided.
3) Order up to three (3) converter modules, P/N
, per module mounting shelf. Each List 60
allows the three right-most shelf positions (when viewed from the front) to accept either converter or
rectifier modules.
List 90: Optional Battery Shunt, 800A
Features
♦
Provides an 800A battery shunt.
Restrictions
For use with List 21 only.
Cannot be used with low voltage load disconnect (LVLD) in a List 21.
Must be ordered with List CA.
Ordering Notes
1) Order as required.
2) Also order
(600A Battery Disconnect Contactor) and either
(Manual Battery Disconnect) or both.
For Use w/ (1)
Rectifier/Converter Shelf
For Use w/ (2
Rectifier/Converter Shelves
For Use w/ (3)
Rectifier/Converter Shelves
For Use w/ (4)
Rectifier/Converter Shelves
For Use w/ (5)
Rectifier/Converter Shelves