SAG582127000
System Application Guide
Issue AF, February 26, 2014
Spec. No. 582127000 (Model 721
NPBB
)
Page 62 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Special Application Crimp Lug / Strap Combination Table
Features
♦
Straps two fuseholder/circuit breaker wiring positions together, and provides a crimp-type lug which
allows distribution wiring up to 350 kcmil size (maximum size of wire to be connected to a single position
is 2 AWG). Designed for use with 125A and larger bullet nose-type circuit breakers or TPS/TLS-type
fuses, which require at least two mounting positions.
Restrictions
If used with bullet nose-type circuit breakers or TPS/TLS-type fuses smaller than 125A, an empty mounting
position is required adjacent to the distribution device.
Ordering Notes
Lead Size
Part Number
1/0 AWG
245393500
2/0 AWG
245393600
3/0 AWG
245393700
4/0 AWG
245393800
250 kcmil
514872
350 kcmil
514873
Table 9
Special Application Crimp Lug / Strap Combination
(Two-Hole Lug, 1/4” Bolt Clearance Hole, 5/8” Centers)