GJ/218 Type Circuit Breakers
Restrictions
For use in Lists AC, AD, BC, and BD.
Load should not exceed 80% of device rating.
Refer to
mounting positions.
Ordering Notes
1) Order circuit breakers as required per
2) Order a jumper kit as required for each
3) See
distribution wire sizes and lugs.
Ampere
Rating
No. of
Positions
P/N
Electrical/
Mechanical Trip
1
without
Internal
Shunt
P/N
Electrical Trip
2
without
Internal
Shunt
Breaker
Mounting
Kit
(without
Shunt)
P/N
Electrical/
Mechanical Trip
1
with
Internal Shunt
(25mV @ full
rated load)
3
P/N
Electrical Trip
2
with
Internal Shunt
(25mV @ full
rated load)
3
Breaker
Mounting
Kit (with
Shunt)
100
1
256621700
256621300
503787
123580
516184
513731
125
1
256621600
256621400
503787
123631
516187
513731
150
1
256621800
256622400
503787
123632
516185
513731
175
1
256621900
256622500
503787
123633
516186
513731
200
1
256622200
256622600
503787
123634
516188
513731
225
1
256622900
256622700
503787
123635
516189
513731
250
1
256623500
256623400
503787
123636
516190
513731
300
2
256625300
103572
513961
550250
550253
554092
400
2
256626200
256626300
513961
550251
550254
554092
600
3
256628200
103571
513957
550252
550255
554093
800
4
121657
121658
554091
--
550249
554094
See
for recommended load distribution wire sizes and lugs.
1, 2
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
3
Extended shunt leads are 22 AWG stranded wire, approximately 7-10 ft. long from exit point at bottom of
distribution cabinet. Each shunt lead is equipped with a 49.9 ohm current limiting resistor. Shunt leads are
factory wired to SM-DU+ (if ordered).
Note:
Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers.
Table 14
GJ/218 Circuit Breakers
GJ/218 Circuit Breakers