Introduction
5
Emerson
®
MPH2
™
Figure 1
Vertical MPH2 rack PDU Configuration
1.1
General Characteristics
• Input ampacities include 16A or 32A for European Union versions and 16A to 48A for North
American versions.
• Single-phase and three-phase.
• Input voltages include 100-120VAC, 120/208VAC, 200-240/415VAC.
• Outlets types include NEMA 5-20, IEC 320 C13 and IEC 320 C19
• Input connection supports a highly flexible fixed power cord or hard-wired connection to user
accessible terminal block.
1.2
Model Types
There are four types of MPH2 rack PDU.
•
Type R
—Outlet Metered, Outlet Switched: Supports metering of the overall input, individual
branches and individual outlets; also supports individual On/Off control of each outlet.
•
Type M
—Outlet Metered: Supports metering of the overall input, individual branches and
individual outlets.
•
Type C
—Rack PDU Metered, Outlet Switched: Supports metering of the overall input and of
individual branches and supports individual On/Off control of each outlet.
•
Type B
—Rack PDU Metered: Provides basic power distribution and supports metering of the
overall input and of the individual branches.
Network
Connection
(10MB/100M
B/1GB)
Monitoring Station
RPC
™
Basic
Display Module
Serial Appliance
Vertical
MPH2
rack PDU
Connected Equipment
Rack PDU Array
™
Sensors
Integrated and
Modular