Oxymitter 5000
E-4
Instruction Manual
IM-106-350, Rev 2.2
July 2008
LO_LO_PRI
54
None
The priority of the LO LO alarm.
LO_PRI
52
None
The priority of the LO alarm.
MATH_FORM
73
None
Selects equation form (series or standard).
MODE_BLK
05
None
The actual, target, permitted, and normal modes of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
OUT
09
EU of OUT SCALE
The block input value and status.
OUT_HI_LIM
28
EU of OUT_SCALE
The maximum output value allowed.
OUT-LO_LIM
29
EU of OUT_SCALE
The minimum output value allowed.
OUT_SCALE
11
None
The high and low scale values, engineering units code, and number of digits
to the right of the decimal point associated with OUT.
PV
07
EU of PV_SCALE
The process variable used in block execution.
PV_FTIME
16
Seconds
The time constant of the first-order PV filter. It is the time required for a 63
percent change in the IN value.
PV_SCALE
10
None
The high and low scale values, engineering units code, and number of digits
to the right of the decimal point associated with PV.
RATE
26
Seconds
The derivative action time constant.
RCAS_IN
32
EU of PV_SCALE
Target setpoint and status that is provided by a supervisory host. Used when
mode is RCAS.
RCAS_OUT
35
EU of PV_SCALE
Block setpoint and status after ramping, filtering, and limiting that is provided
to a supervisory host for back calculation to allow action to be taken under
limiting conditions or mode change. Used when mode is RCAS.
RESET
24
Seconds per repeat
The integral action time constant.
ROUT_IN
33
EU of OUT_SCALE
Target output and status that is provided by a supervisory host. Used when
mode is ROUT.
ROUT_OUT
36
EU of OUT_SCALE
Block output that is provided to a supervisory host for a back calculation to
allow action to be taken under limiting conditions or mode change. Used
when mode is RCAS.
SHED_OPT
34
None
Defines action to be taken on remote control device time-out.
SP
08
EU of PV_SCALE
The target block setpoint value. It is the result of setpoint limiting and setpoint
rate of change limiting.
SP_FTIME
69
Seconds
The time constant of the first-order SP filter. It is the time required for a 63
percent change in the IN value.
SP_HI_LIM
21
EU of PV_SCALE
The highest SP value allowed.
SP_LO_LIM
22
EU of PV_SCALE
The lowest SP value allowed.
SP_RATE_DN
19
EU of PV_SCALE per
second
Ramp rate for downward SP changes. When the ramp rate is set to zero, the
SP is used immediately.
SP-RATE_UP
20
EU of PV_SCALE per
second
Ramp rate for upward SP changes. When the ramp rate is set to zero, the SP
is used immediately.
SP_WORK
68
EU of PV_SCALE
The working setpoint of the block after limiting and filtering is applied.
STATUS_OPTS
14
None
Allows you to select options for status handling and processing. The
supported status option for the PID block is Target to Manual if Bad IN.
STRATEGY
03
None
The strategy field can be used to identify grouping of blocks. This data is not
checked or processed by the block.
ST_REV
01
None
The revision level of the static data associated with the function block. The
revision value will be incremented each time a static parameter value in the
block is changed.
STRUCTURE.
CONFIG
75
None
Defines PID equation structure to apply controller action.
TAG_DESC
02
None
The user description of the intended application of the block.
TRK_IN_D
38
None
Discrete input that initiates external tracking.
Parameter
Index
Number
Units
Description
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 12: ......
Page 22: ...Oxymitter 5000 xii Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 42: ...Oxymitter 5000 1 20 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 62: ...Oxymitter 5000 2 20 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 74: ...Oxymitter 5000 4 6 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 78: ...Oxymitter 5000 5 4 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 94: ...Oxymitter 5000 7 6 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 140: ...Oxymitter 5000 9 22 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 184: ...Oxymitter 5000 B 2 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 204: ...Oxymitter 5000 D 14 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 222: ...Oxymitter 5000 E 18 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 224: ...Instruction Manual IM 106 350 Rev 2 2 July 2008 Index 2 Oxymitter 5000 ...