PACMotion™ Servos Accessories Guide
Section 9
GFK-3173C
December 2020
Cables
28
9.5
Motor Feedback Cable Specifications
All cables supplied with PSD servo drives
are RoHS compliant.
9.5.1
Cable Routing Standards
UL 508C and UL 508A indicate that wires, when routed together, shall be rated for the highest voltage
involved in all of the circuits. This means that value line feedback cables which are 300 V rated are not
appropriate when routed directly next to motor power cables that carry more voltage than 300 V. They
should be physically separated. Performance line cables are recommended when this is a concern.
The NFPA 70 (NEC) article 300.3(C)(1) says that for circuits that are 600 V or less, conductors of ac and dc
circuits shall be permitted to occupy the same equipment wiring enclosure, cable, or raceway. All
conductors shall have an insulation rating equal to at least the maximum circuit voltage applied to any
conductor within the enclosure, cable, or raceway.