GFK-3111A
PACMotion VFD AC Variable Speed Drive User Guide
85
Table 57: 380 – 480 Volt (+ / - 10%), 3 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated Output
Current
Maximum Motor
Cable Length
Recommended
Brake Resistance
kW
HP
A
Non UL UL
mm AWG/kcmil A
m
ft
Ω
2
0.75 1
3.5
6
6
8
8
2.2
100
330
400
2
1.5
2
5.6
10
10
8
8
4.1
100
330
200
2
2.2
3
7.5
10
10
8
8
5.8
100
330
150
2
4
5
11.5
16
15
8
8
9.5
100
330
100
3
5.5
7.5
17.2
25
25
8
8
14
100
330
75
3
7.5
10
21.8
32
30
8
8
18
100
330
50
3
11
15
27.5
40
35
8
8
24
100
330
40
4
15
20
34.2
50
45
16
5
30
100
330
22
4
18.5 25
44.1
63
60
16
5
39
100
330
22
4
22
30
51.9
63
70
16
5
46
100
330
22
5
30
40
66.1
80
80
35
2
61
100
330
12
5
37
50
77.3
100
100
35
2
72
100
330
12
6
45
60
102.7
125
125
150 300MCM
90
100
330
6
6A
45
60
83.5
125
110
150 300MCM
90
100
330
6
6
55
75
126.4
125
175
150 300MCM
110
100
330
6
6A
55
75
102.2
125
125
150 300MCM
110
100
330
6
6
75
100 164.7
200
200
150 300MCM
150
100
330
6
6B
75
100 144.1
200
175
150 300MCM
150
100
330
6
6
90
150 192.1
250
250
150 300MCM
180
100
330
6
6B
90
150 167.4
250
225
150 300MCM
180
100
330
6
6B
110 175 189.8
250
250
150 300MCM
202
100
330
6
7
110 175 210.8
250
300
150 300MCM
202
100
330
6
7
132 200 241.0
315
300
150 300MCM
240
100
330
6
7
160 250 299.0
400
400
150 300MCM
302
100
330
6
8
200 300 377.2
500
500
240 450MCM
370
100
330
3
8
250 350 458.7
600
600
240 450MCM
450
100
330
3
Table 58: 480 – 525 Volt (+/- 10%), 3 phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated Output
Current
Maximum Motor
Cable Length
Recommended
Brake Resistance
kW
HP
A
Non UL UL
mm AWG/kcmil A
m
ft
Ω
7
132
192
250
150 300MCM
185
100
330
7
7
160
215
315
150 300MCM
205
100
330
7
7
185
262
315
150 300MCM
255
100
330
7
7
200
275
400
150 300MCM
275
100
330
7