PACSystems Ethernet Switch SLM080 User Manual
Section 6
GFK-3125A
Jan 2020
Command Line Interface Management
93
6.14
Commands Set List
―
SYSLOG, SMTP, EVENT command
set
SLM080Commands
Level
Description
Example
systemlog ip
[IP address]
G
Set System log server IP
address.
switch(config)# systemlog ip
192.168.1.100
systemlog mode
[client|server|both]
G
Specified the log mode
switch(config)# systemlog mode
both
show systemlog
E
Display system log.
Switch>show systemlog
show systemlog
P
Show system log client &
server information
switch#show systemlog
no systemlog
G
Disable systemlog function
switch(config)#no systemlog
smtp enable
G
Enable SMTP function
switch(config)#smtp enable
smtp serverip
[IP address]
G
Configure SMTP server IP
switch(config)#smtp serverip
192.168.1.5
smtp authentication
G
Enable SMTP authentication
switch(config)#smtp
authentication
smtp account
[account]
G
Configure authentication
account
switch(config)#smtp account
User
smtp password
[password]
G
Configure authentication
password
switch(config)#smtp password
smtp rcptemail
[Index] [Email
address]
G
Configure Rcpt e-mail Address
switch(config)#smtp rcptemail 1
show smtp
P
Show the information of SMTP
switch#show smtp
no smtp
G
Disable SMTP function
switch(config)#no smtp
event device-cold-start
[Systemlog|SMTP|Bot
h]
G
Set cold start event type
switch(config)#event device-
cold-start both
event authentication-
failure
[Systemlog|SMTP|Bo
th]
G
Set Authentication failure
event type
switch(config)#event
authentication-failure both