MODEL MGS-314L SERIES LEVEL CONTROL SWITCH

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Before installation, these instructions must be carefully read and understood.

Emerson.com/FinalControl

© 2019 Emerson. All Rights Reserved.

VCIOM-03389-EN 20/04

PRODUCT WARRANTY

Emerson warrants its products as designed 
and manufactured to be free of defects in 
material and workmanship for a period of one 
year after the date of installation or eighteen 
months after date of manufacture, whichever 
is earliest. Emerson will, at its option, replace 
or repair any products which fail during the 
warranty period due to defective material or 
workmanship.

Prior to submitting any claim for warranty 
service, the owner must submit proof of 
purchase to Emerson and obtain written 
authorization to return the product. Thereafter, 
the product shall be returned to Emerson, with 
freight prepaid.

This warranty shall not apply if the product has 
been disassembled, tampered with, repaired 
or altered outside of the Emerson factory, or 
if it has been subjected to misuse, neglect or 
accident.

TABLE OF CONTENTS

  Product Warranty .......................................... 1
1. Introduction ................................................... 1
2. Specifications/Approvals .............................. 2
  2.1  2.1 Enclosure .......................................... 2
  2.2 Switch ...................................................... 2
  2.3 Approvals ................................................ 2
3.  Theory of Operation ....................................... 2
4. Installation ..................................................... 3
  4.1 Unpacking ............................................... 3
  4.2  Mounting the switch ............................... 3

 

4.3  Wiring connection................................... 3

5. Set-up ............................................................. 4
  5.1  Initial test ................................................ 4
6. Troubleshooting ............................................ 4
  6.1 Introduction ............................................ 4
  6.2  Switch test .............................................. 4
7.  Disposal at End of Useful Life ...................... 4
8.  Telephone Assistance ................................... 4

Emerson's responsibility hereunder is limited 
to repairing or replacing the product at its 
expense.
Emerson shall not be liable for loss, damage, 
or expenses directly or indirectly related to the 
installation or use of its products, or from any 
other cause or for consequential damages. It 
is expressly understood that Emerson is not 
responsible for damage or injury caused to 
other products, building, property or persons, 
by reason of the installation or use of its 
products.

This is Emerson's sole warranty and in lieu of 
all other warranties, expressed or implied which 
are hereby excluded, including in particular all 
warranties of merchantability or fitness for a 
particular purpose.

This document and the warranty contained 
herein may not be modified and no other 
warranty, expressed or implied, shall be made 
by or on behalf of Emerson unless modified or 
made in writing and signed by the company's 
president or a vice president.

1 INTRODUCTION

The instructions in this manual pertain to the 
Penberthy Model MGS-314L Series magnetic 
level gauge switch.
The Model MGS-314L Series magnetic level 
gauge switch is designed to detect the passage 
of the float in a Multiview™ magnetic liquid 
level gauge, at a specific location. The switch 
consists of a bi-stable latching reed switch 
encased in a watertight enclosure.

Tables and Figures

Table 1 

 Wire conditions at different 
switch orientations .......................... 4

Figure 1  MGS-314L switch positions ............ 2
Figure 2   Control drawing CSA approved 

explosion-proof for 
MGS-314L (7E741-008) ................... 5

Figure 3   Control drawing CSA approved 

intrinsically safe for 
MGS-314L (7E742-008) ................... 6

Figure 4   Control drawing ATEX/ 

IECEx certified explosion-proof 
for MGS-314L (7E741-010)  ............. 7

Figure 5   Control drawing ATEX/ 

IECEx certified intrinsically safe  
for MGS-314L (7E741-010)  ............. 8

Summary of Contents for PENBERTHY MGS-314L Series

Page 1: ...epairing or replacing the product at its expense Emerson shall not be liable for loss damage or expenses directly or indirectly related to the installation or use of its products or from any other cause or for consequential damages It is expressly understood that Emerson is not responsible for damage or injury caused to other products building property or persons by reason of the installation or u...

Page 2: ...rawing 7E742 008 Figure 3 MGS 314L A ATEX and IECEx approved by CSA Flame proof for Ex db IIB T5 Gb 1 A Max or 150Vdc Max Must use suitably certified minimum Ex db IIB conduit seal When installed in accordance with control drawing 7E741 010 Figure 4 MGS 314L A ATEX and IECEx approved by CSA Intrinsically safe for Ex ia IIC T5 Ga When installed in accordance with control drawing 7E742 010 Figure 5 ...

Page 3: ...he indication range This will insure sufficient float movement to operate the switch 7 If more than one switch is used on a single magnetic gauge the minimum recommended distance between mounting bands is 2 inches 51 mm 8 Adjust the position of the indicating scale so that the distance from the tip of the scale to the top of the communicating chamber is the same as in step 1 Tighten the clamps hol...

Page 4: ... occur Sound maintenance practices require periodic inspection of the instrument to ensure it is in good working order SAFETY INSTRUCTIONS Do not apply power to the switch while performing these tests 6 2 Switch test With the switch at position A use an ohmmeter to verify the conditions in Section 5 1 Using a magnet move the switch to position B If the switch still doesn t change state it is defec...

Page 5: ...IV I GROUP B C D CONTROL DRAWING Hazardous area Non hazardous area A flame path seal off shall be installed within 18 in of enclosure Wiring to be in accordance with National Electrical Code NEC Pertinent parts of the 500 Series of Article 5 or local codes as applicable FIGURE 2 Control drawing CSA approved explosion proof for MGS 314L 7E741 008 18 ...

Page 6: ...sc 150mA Ca Cleads La Lleads THREE WIRE ENTITY CONTROL DRAWING Non hazardous area Hazardous area User wiring INTRINSIC SAFETY BARRIER MULTIPLE CHANNEL Cleads Lleads Use CSA certified safety barriers rated for Class I DIV 1 Group A B C D One multiple channel intrinsic safety barrier must be used The barrier parameters must meet the following requirements Vt 40V or It 150mA Ca Cleads La Lleads MODEL...

Page 7: ...us area A flame path seal off shall be installed directly to threaded entry of enclosure Wiring to be in accordance with National Electrical Code NEC Pertinent parts of the 500 Series of Article 5 or local codes as applicable FIGURE 4 Control drawing ATEX IECEx certified explosion proof for MGS 314L 7E741 010 MGS 314 A MGS 314D A MGS 314L A EX D IIB ...

Page 8: ...oc 40V or Isc 150mA Ca Cleads La Lleads One multiple channel intrinsic safety barrier must be used The barrier parameters must meet the following requirements Vt 40V or It 150mA Ca Cleads La Lleads Installation shall confirm to the manufacturer s instructions supplied with the intrinsic safety barrier as well as the National Electric Code and ANSI ISA RP 12 6 or CSA C22 Installation of intrinsical...

Page 9: ...rson logo are trademarks and service marks of Emerson Electric Co All other marks are the property of their respective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or th...