background image

Quick Start Guide

5

February 2014

a. Depressurize the line using site-specific requirements.
b. Loosen all studs and nuts.
c. Remove the studs in one-half of the flange union.
d. Spread flange union by turning jackscrews clockwise.
e. Install the new plate or remove the existing plate for replacement or 

inspection.

f. Install the new gaskets when installing the plate. It is recommended that 

new gaskets be installed each time the orifice flange union is separated.

g. Center the plate in the pipe I.D.
h. Release the flange union by turning the jackscrews counter-clockwise. 
i. Replace the studs.
j. Tighten studs in a star pattern.

Figure 1.  Rosemount 1495 installation

Nuts

Transmitter

Stud

Pipe 
Section

1595

(1)

Jackscrew (2)

Plug (2)

Nut

Gasket (2)

Jackscrew

Nut

Flo

w

(1)  The installation drawings applies when using the Rosemount 3051S, Rosemount 3051C, 

and Rosemount 3095MV transmitter. See the following documents for quick installation instruction of the 
transmitters.
Rosemount 3051S: document number 00825-0100-4801
Rosemount 3051C: document number 00825-0100-4001
Rosemount 3095MV: document number 00825-0100-4716

Jackscrew 

Nut

4792_ QIG_Rev BB.fm  Page 5  Thursday, February 13, 2014  8:46 AM

Summary of Contents for Rosemount 1495

Page 1: ...Quick Start Guide 00825 0100 4792 Rev BB February 2014 Rosemount 1495 Orifice Plate Rosemount 1496 Orifice Flange Union ...

Page 2: ...I S installations Refer to the 1495 reference manual document number 00809 0100 4792 for more instruction This manual is also available electronically on www rosemount com Process leaks may cause harm or result in death To avoid process leaks only use gaskets designed to seal with the corresponding flange and o rings to seal process connections Contents Primary element location page 3 Primary elem...

Page 3: ...ual 00809 0100 4792 for a list of required straight pipe recommendations based on ISO 5167 AGA Report No 3 and ASME MFC 3M Standards Shorter straight runs are possible but accuracy will be affected per the Standards Consult the Factory for further information Step 2 Primary element orientation Horizontal pipe installation Gas Steam Liquid FLOW 30 degrees Recommended Zone 120 degrees 30 degrees Flo...

Page 4: ...owing steps to install the 1495 Orifice Plate paddle or universal plate style 1 Determine Location and Orientation see page 3 2 Install the Orifice Plate Gas Steam Liquid FLOW Flow Flow HI Instrument Line LO Transmitter Connection LO Instrument Line Flow Bring height of HI instrument line to the same height as LO instrument line before running down to the transmitter HI Instrument Line LO Transmit...

Page 5: ...ated g Center the plate in the pipe I D h Release the flange union by turning the jackscrews counter clockwise i Replace the studs j Tighten studs in a star pattern Figure 1 Rosemount 1495 installation Nuts Transmitter Stud Pipe Section 1595 1 Jackscrew 2 Plug 2 Nut Gasket 2 Jackscrew Nut Flow 1 The installation drawings applies when using the Rosemount 3051S Rosemount 3051C and Rosemount 3095MV t...

Page 6: ...installation drawings applies when using the Rosemount 3051S Rosemount 3051C and Rosemount 3095MV transmitter See the following documents for quick installation instruction of the transmitters Rosemount 3051S document number 00825 0100 4801 Rosemount 3051C document number 00825 0100 4001 Rosemount 3095MV document number 00825 0100 4716 Jackscrew 1495 1 ...

Page 7: ...found on the Rosemount website at www rosemount com A hard copy may be obtained by contacting our local sales office European Pressure Equipment Directive PED 97 23 EC Rosemount 1495 Orifice Plate Sound Engineering Practice SEP Pressure Transmitter See appropriate Pressure Transmitter QIG Hazardous locations certifications For information regarding the electronics product certification see the app...

Page 8: ...8153 9390 F49 8153 939172 Beijing Rosemount Far East Instrument Co Limited No 6 North Street Hepingli Dong Cheng District Beijing 100013 China T 86 10 6428 2233 F 86 10 6422 8586 2014 Rosemount Inc All rights reserved All marks property of owner The Emerson logo is a trade mark and service mark of Emerson Electric Co Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc M...

Reviews: