11
Reference Manual
00809-0300-4410, Rev BA
Configuration
January 2018
Configuration
Figure 2-6. LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
Table 2-2. LOI Button Operation
2.6.3
Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of the
transmitter, set the process application loop to manual control. The Field Communicator, AMS Device
Manager, or the LOI will prompt you to set the loop to manual when necessary. The prompt is only a
reminder; acknowledging this prompt does not set the loop to manual. It is necessary to set the loop to
manual control as a separate operation.
2.7
Verify configuration
It is recommended that various configuration parameters are verified prior to installation into the
process. The various parameters are detailed out for each configuration tool. Depending on what
configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1
Field Communicator
Configuration parameters listed in
are to be reviewed prior to transmitter installation. A full list
of configuration parameters that can be reviewed and configured using a Field Communicator is located
in
Appendix B: Field Communicator Menu Trees and Fast Keys
Fast key sequences for the latest DD are shown in
. For Fast Key sequences for legacy DD's
contact your local Emerson Representative.
Button
Left
No
SCROLL
Right
Yes
ENTER
B
A
Summary of Contents for Rosemount 2051G
Page 2: ......
Page 10: ...2 Reference Manual 00809 0400 4101 Rev BA Introduction January 2018 Introduction ...
Page 34: ...26 Reference Manual 00809 0300 4410 Rev BA Configuration January 2018 Configuration ...
Page 72: ...64 Reference Manual 00809 0400 4101 Rev BA Troubleshooting January 2018 Troubleshooting ...
Page 89: ......