Incorrect temperature
measurement
Incorrect configuration
•
Check temperature element configuration. See the
Gauging System Configuration Manual
for more information on how
to use TankMaster Winsetup for configuration of temperature
elements connected to the Rosemount 2240S.
•
Check status and diagnostics information, see
•
Check Model Code to verify that the correct options are available.
Temperature element failure
•
Check diagnostics information, see
.
•
Check Device Status input register, see
•
Check temperature element status, see
.
•
Use the built-in temperature element simulator to check the
Rosemount 2240S electronics, see
•
Replace malfunctioning temperature elements.
Configuration can not be
saved
Write protection switch is set to
the ON position
•
Check write protection switch, see
.
The Status LED is blinking
error codes
Rosemount 2240S transmitter,
temperature element, or Water
Level Sensor error
•
Check the Rosemount 2240S for possible hardware or software
errors.
•
Check temperature elements.
•
Check Water Level Sensor.
•
See
“Device error LED signals” on page 113
•
See
•
Check Device Status input register (see
).
•
Contact Emerson Automation Solutions/Rosemount TankGauging
service department.
Rosemount 2240S icon in
TankMaster WinSetup is
red
Simulation mode active
•
Stop Simulation mode by setting the Simulate switch to OFF (see
•
Stop Simulation mode in TankMaster WinSetup (open WinSetup Set
Simulation Mode window and click the Stop button).
Symptom (continued)
Possible cause
Action
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......