Reference Manual
00809-0100-4570, Rev DA
Connection via Modbus RTU
November 2017
Connection via Modbus RTU
159
Appendix B
Connection via Modbus RTU
Initial settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 159
Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 160
Communication examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 160
Note
These instructions apply to a direct connection between the DCS/SCADA system to the Rosemount
™
5708 3D Solids Scanner directly.
B.1
Initial settings
COM port settings:
Baud rate = 115200
Data bits = 8
Parity = None
Stop bits = 1
In order to get the values from the device, a Modbus
®
RTU command with function code 3 should be
executed.
The address of the device equals its polling a 1.