Electrical Installation
November 2017
Electrical Installation
4.5
Different connection methods
4.5.1
4-20 mA connection
The Rosemount 5708 outputs the % of Volume as set in the configuration and between the Full and
Empty calibration levels. The 4-20mA current output is available through ports 3 and 4 of the left green
terminal block (as shown in
). Ports 3 and 4 are the negative and positive poles, respectively.
Figure 4-3. Port 3 and 4
The 4-20mA line is connected directly from the Rosemount 5708 mounted on the vessel to the
PLC/DCS/Display or any other device (as shown in
Figure 4-4. Rosemount 5708 Connected to PLC
A. Active
B. 4-20 mA
C. Passive
D. PLC/Controller
Note
The maximum cable length of a 4-20 mA cable can be up to 2 miles (3 km).
This type of connection is active and not passive, hence the Rosemount 5708 is the active
module and the PLC should be the passive module.