4.2
Overview
The Rosemount
™
5900C can be installed in Rosemount Tank Gauging systems including
Rosemount 2460 System Hubs and Rosemount 2410 Tank Hubs. The Rosemount 5900C
also supports installation in F
OUNDATION
™
information.
Installation of the Rosemount 5900C is a simple and straight-forward procedure. In a
Rosemount Tank Gauging system with Rosemount 2410 Tank Hub and Rosemount 2460
System Hub it basically includes the following steps:
1. Preparations: make a note of Unit ID, Modbus address
geometry parameters such as tank height, tank type, strapping table.
2. Set up communication protocol and communication parameters.
3. Configuration of the Rosemount 2460 System Hub.
4. Configuration of the Rosemount 2410 Tank Hub.
5. Configuration of field devices such as the Rosemount 5900C Radar Level Gauge and
the Rosemount 2240S Multiple-Input Temperature Transmitter.
6. Calibration of the Rosemount 5900C.
Installation of the Rosemount 5900C in F
OUNDATION
Fieldbus systems is supported by a
complete set of Resource, Function, and Transducer blocks. You can easily integrate the
level gauge into any existing F
OUNDATION
Fieldbus network by using an appropriate
configuration tool such as the AMS Device Manager. See section
The Rosemount
™
TankMaster
™
WinSetup program is the recommended tool for
installation and configuration of a Rosemount 5900C Radar Level Gauge in systems that
include a Rosemount 2410 Tank Hub. The Rosemount 5900C is preferably installed as part
of the procedure when installing a tank hub:
1. Install and configure the Rosemount 2410 Tank Hub by using the device installation
wizard in TankMaster WinSetup.
2. Ensure that automatic installation of field devices is enabled when finishing the tank
hub installation. The Rosemount 2410 Tank Hub, Rosemount 5900C Level Gauge,
and other field devices on the Tankbus will automatically appear in the WinSetup
workspace.
3. Configure the Rosemount 5900C level gauge via the
Properties
window.
If a Rosemount 5900C level gauge is added to an existing system, the tank hub’s database
must be updated before the level gauge is configured. The tank database maps the level
gauge to the tank on which it is installed.
A detailed description of how to install and configure a Rosemount 5900C and other
devices by using the Rosemount TankMaster WinSetup software is provided in the
Rosemount Tank Gauging
.
(9)
See the Rosemount Tank Gauging
.
Configuration
Reference Manual
September 2019
00809-0100-5901
118
Reference Manual
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...