changes to all configurable parameters. The target mode of a block
may be restricted to one or more of the supported modes.
4.11.4
Application example
Level value
A Rosemount 5900C Radar Level Gauge measures the product level in a 15 m high tank.
Table 4-7: Analog Input Function Block Configuration for a Rosemount 5900C Level
Gauge
Parameter
Configured Values
L_TYPE
Direct
XD_SCALE
EU_0=0. EU_100=15. Engineering unit=meter.
OUT_SCALE
EU_0=0. EU_100=15. Engineering unit=meter.
CHANNEL
CH1: Level
4.11.5
Simulation
To perform lab test of process variables and alerts, you can either change the mode of the
AI block to manual and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and its status. In
both cases, you must first set the SIMULATE switch (1) on the field device to the ON
position.
With simulation enabled, the actual measurement value has no impact on the OUT value
or the status.
Configuration
Reference Manual
September 2019
00809-0100-5901
164
Reference Manual
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...