Table C-1: Resource Block Parameters
(continued)
Index
Number
Parameter
Description
39
WRITE_PRI
Priority of the alarm generated by clearing the write lock.
40
WRITE_ALM
This alert is generated if the write lock parameter is cleared.
41
ITK_VER
Major revision number of the inter operability test case used in certifying
this device as interoperable. The format and range are controlled by the
Fieldbus Foundation.
42
FD_VER
A parameter equal to the value of the major version of the Field
Diagnostics specification that this device was designed to.
43
FD_FAIL_ACTIVE
This parameter reflects the error conditions that are being detected as
active as selected for this category. It is a bit string, so that multiple
conditions may be shown.
44
FD_OFFSPEC_ACTIVE
45
FD_MAINT_ACTIVE
46
FD_CHECK_ACTIVE
47
FD_FAIL_MAP
This parameter maps conditions to be detected as active for this alarm
category. Thus the same condition may be active in all, some, or none of
the 4 alarm categories.
48
FD_OFFSPEC_MAP
49
FD_MAINT_MAP
50
FD_CHECK_MAP
51
FD_FAIL_MASK
This parameter allows the user to suppress any single or multiple
conditions that are active, in this category, from being broadcast to the
host through the alarm parameter. A bit equal to ‘1’ will mask i.e. inhibit
the broadcast of a condition, and a bit equal to ‘0’ will unmask i.e. allow
broadcast of a condition.
52
FD_OFFSPEC_MASK
53
FD_MAINT_MASK
54
FD_CHECK_MASK
55
FD_FAIL_ALM
This parameter is used primarily to broadcast a change in the associated
active conditions, which are not masked, for this alarm category to a
Host System.
56
FD_OFFSPEC_ALM
57
FD_MAINT_ALM
58
FD_CHECK_ALM
59
FD_FAIL_PRI
This parameter allows the user to specify the priority of this alarm
category.
60
FD_OFFSPEC_PRI
61
FD_MAINT_PRI
62
FD_CHECK_PRI
63
FD_SIMULATE
This parameter allows the conditions to be manually supplied when
simulation is enabled. When simulation is disabled both the diagnostic
simulate value and the diagnostic value tracks the actual conditions. The
simulate jumper is required for simulation to be enabled and while
simulation is enabled the recommended action will show that simulation
is active.
Elements: see
F
OUNDATION
™
Fieldbus Block Information
Reference Manual
September 2019
00809-0100-5901
294
Reference Manual
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...