Specifications and reference data
A.1
General
A.1.1
Instrument accuracy
± 2.0 mm (0.08 in.)
Instrument accuracy is under reference conditions. Reference conditions are:
Measurement in test bench at Rosemount Tank Radar AB in Mölnlycke Sweden. Test
bench is calibrated minimum yearly by an accredited laboratory (SP Technical Research
Institute of Sweden. Measuring range is up to 30 m (98 ft). Ambient temperature and
humidity is close to constant during tests. Total uncertainty in test bench is below 0.15
mm (0.006 in.).
A.1.2
Temperature stability
Typically < ± 0.5 mm (0.020 in.) in -40 to +70 °C (-40 to +158 °F)
A.1.3
Fieldbus (standard)
F
OUNDATION
™
Fieldbus FISCO (Tankbus)
A.1.4
Update time
New measurement every 0.3 s
A.1.5
Repeatability
0.2 mm (0.008 in.)
A.1.6
Maximum level rate
Up to 200 mm/s
A.1.7
Metrology sealing possibility
Yes
A.1.8
Installation considerations
.
Reference Manual
Specifications and reference data
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
245
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...