Table C-3: Definitions of Analog Input Function Block System Parameters
(continued)
Index Number Parameter
Units
Description
38
ALARM_SEL
None
Used to select the process alarm conditions that will cause the
OUT_D parameter to be set.
39
STDDEV
Percent
The average absolute error between the PV and its previous mean
value over that evaluation time defined by VAR_SCAN.
40
CAP_STDDEV
Seconds
The time over which the VAR_INDEX is evaluated.
C.2.1
Simulation
To perform lab test of process variables and alerts, you can either change the mode of the
AI block to manual and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and its status. In
both cases, you must first set the SIMULATE switch (1) on the field device to the ON
position, see
With simulation enabled, the actual measurement value has no impact on the OUT value
or the status.
C.3
Analog Output block
Figure C-3: Analog-Output Block
%
$
&
A. CAS_IN = The remote setpoint value from another function block
B. BKCAL_OUT = The value and status required by the BKCAL_IN input of another block to
prevent reset windup and to provide bumpless transfer to closed loop control.
C. OUT = The block output value and status
The Analog Output (AO) function block assigns an output value to a field device through a
specified I/O channel. The block supports mode control, signal status calculation, and
simulation.
lists the definitions of the system parameters. See also
Table C-4: Analog Output Function Block System Parameters
Parameter
Units
Description
BKCAL_OUT
EU of PV_SCALE The value and status required by the BKCAL_IN input of
another block to prevent reset windup and to provide
bumpless transfer to closed loop control.
Reference Manual
F
OUNDATION
™
Fieldbus Block Information
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
301
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...