Update rate considerations
Before configuring the wireless update rate for your wireless devices, evaluate the safety
concerns, conditions, and wireless network in your facility to select the current update rate
to meet your needs.
When specifying the update rate, consider the potential for toxic gas release, the severity
of potential gas concentration that may be released, and whether the device is located in a
populated area. The default update rate is eight seconds and is appropriate for most
applications. You may use a more frequent update rate if desired. A less frequent update
rate extends transmitter power module life and optimizes Wireless Gateway device
capacity.
Consider the speed with which you want to be alerted to a dangerous condition of toxic
gas. Emerson does not recommend reporting by exception for the Rosemount 928
Wireless Gas Monitors or Emerson Wireless Gateways due to its potential adverse effect on
Wireless Gateway capacity and network integrity. Therefore, select an update rate for all
wireless gas monitors that corresponds to the safety needs of your facility but does not
exceed the capacity of the Wireless Gateway or your wireless network.
Reference Manual
Configuration
00809-0100-4928
September 2019
Rosemount 928
31
Summary of Contents for Rosemount 928
Page 1: ...Reference Manual 00809 0100 4928 Rev AE September 2019 Rosemount 928 Wireless Gas Monitor ...
Page 4: ...4 ...
Page 8: ...Contents Reference Manual September 2019 00809 0100 4928 viii Emerson com Rosemount ...
Page 106: ...Configuration Reference Manual September 2019 00809 0100 4928 106 Emerson com Rosemount ...
Page 178: ...Troubleshooting Reference Manual September 2019 00809 0100 4928 178 Emerson com Rosemount ...