6. Select
Next
to confirm successful process alert configuration.
7. Select
Finish
.
2.8
Calibrating the sensor
Calibrating the sensor ensures that the analog, digital, and discrete outputs accurately
transmit the target gas concentrations registered by the module. Although Emerson
calibrated the device at the factory, you must calibrate it at the following times to ensure
accuracy and correct operation:
•
During installation.
•
At least every 90 days throughout the device's service life.
•
When replacing the sensor.
The Rosemount 628 Universal Gas Sensor is a smart sensor. As such, it retains its own
calibration information. It must be connected to a transmitter to calibrate, but the
calibration settings are stored in the sensor itself rather than in the transmitter. You may
uninstall the sensor from a transmitter and reinstall it in another transmitter without
affecting its calibration.
CAUTION
If you are calibrating in a windy environment (over five mph), a calibration cup must be
used to ensure calibration accuracy.
Reference Manual
Configuration
00809-0100-4928
September 2019
Rosemount 928
47