Select Read Next Record to go to the next record in the sensor log based on the
selected database search method. This is the default option.
•
Select Show Additional Status to view more information from the selected
record. This option is available only if additional information is available for the
selected record.
•
Select Exit to leave the sensor log.
7. When you have finished viewing sensor log records, select
Exit
.
8. Select
Finish
.
5.8
Bump testing
Bump testing is a process by which the target gas is introduced to the sensor to verify that
the device is functioning properly. Bump testing does not replace calibration. Emerson
recommends bump testing throughout the sensor's service life as prescribed by your
facility preventative maintenance procedures.
If bump testing fails, recalibrate the sensor. Refer to
fails to accept a new calibration, replace it. Refer to
Reference Manual
Operation and maintenance
00809-0100-4928
September 2019
Rosemount 928
159