Section 2: Initial Connection
February 2014
Initial Connection
2.3.6
Resetting to factory defaults
In the event that the user name, password, or IP address of the Gateway is lost, the Gateway can
be restored to factory defaults by the procedure below.
Note
Following this procedure will cause the network to reform and all configuration parameters will
be reset to factory defaults. Once the Gateway is reset, the user is strongly recommended to
change the default password to maintain system security.
1.
Turn off power to the Gateway, remove connectors, and un-mount the device from the
DIN rail.
2.
Locate the
Reset
switch label on the back of the Gateway.
3.
Break the label in the center and slide the switch up.
4.
Mount and reconnect the Gateway; turn power
ON
on to the gateway.
5.
Let the Gateway completely boot up (approximately 2 minutes). During this time the
red
Reset
light on the front of the unit will be
ON
.
6.
Turn off power to the Gateway, remove connectors and un-mount it from the rail again.
7.
Return the
Reset
switch to lower position.
8.
Mount and reconnect the Gateway; turn power ON on to the Gateway.
9.
Verify the reset light is off, indicating the
Reset
switch is in the lower position. The
Gateway will now be programmed back to factory defaults including IP addresses. The
factory default IP addresses can be found in
Table 2-1 on page 7