Section 6: Troubleshooting
February 2014
Troubleshooting
Section 6
Troubleshooting
This section provides basic troubleshooting tips for the Smart Wireless Field Network. To receive
technical support by phone:
Global Service Center
Software and Integration support
United States – 1 800 833 8314
International – 63 2 702 1111
Customer Central
Technical support, quoting, and order-related questions
United States – 1 800 999 9307 (7:00 am to 7:00 pm CST)
Asia Pacific – 65 6777 8211
Europe / Middle East / Africa – 49 (8153) 9390
Or email the wireless specialists at:
Specialists-Wireless.EPM-RTC@EmersonProcess.com
Initial connection
Web browser returns page not
found
1. Connect the Gateway and PC/Laptop
2. Verify the Gateway is properly powered, 24 VDC (nominal) and 250 mA.
3. Verify which Ethernet port is being used on the Gateway.
4. Verify the IP address for the Gateway (default primary port is 192.168.1.10, default
secondary port is 192.168.2.10 or for DeltaV Ready Gateway’s default primary port
is 10.5.255.254, default secondary port is 10.9.255.254).
5. Verify the IP address of the PC/Laptop is in the same subnet range as the Gateway
(i.e. If the Gateway IP is 155.177.0.xxx, then the PC/Lap IP address should be
155.177.0.yyy).
6. Disable internet browser proxy settings.
Can not find Gateway after
changing IP address
1. Verify the IP address of the PC/Laptop is in the same subnet range as the Gateway
(i.e. If the Gateway IP is 155.177.0.xxx, then the PC/Lap IP address should be
155.177.0.yyy). Consider resetting the gateway to factory defaults.
Can not find Gateway using
Secondary Ethernet Port
1. Verify which Ethernet port is being used on the Gateway.
2. Verify the IP address for the Gateway (default primary port is 192.168.1.10, default
secondary port is 192.168.2.10).
3. Verify the IP address of the PC/Laptop is in the same subnet range as the Gateway
(i.e. If the Gateway IP is 155.177.0.xxx, then the PC/Lap IP address should be
155.177.0.yyy). Verify this option was ordered with the Gateway.
Can not log into the Gateway
1. Verify the user name and password. The administrator user name is admin and the
default password is default. See
Table 2-1
. If unable to connect, consider resetting
the Gateway.