57
Reference Manual
00809-0200-4410, Rev BA
Appendix A: Product Specifications
February 2014
Product specifications
A.2
Functional specifications
Input voltage
10.5-30 VDC Class 2 Power Supply
Current draw
Operating current draw is based on 3.0 Watt power consumption.
Radio frequency power output from antenna
Maximum of 10 mW (10 dBm) EIRP for WL or WX antenna types
Maximum of 40 mW (16 dBm) EIRP for WN2 high gain option
Environmental
Operating Temperature Range:
-40 to 167 °F (-40 to 75 °C)
Operating Humidity Range:
0-100% relative humidity
EMC performance
Complies with EN61326-1:2006.
Antenna options
Optional remote mount omnidirectional antenna
Antenna
2 dBi rubber dipole with SMA connector
SMA connection is female
12
24
30
125
250
Voltage (VDC)
Cu
rr
e
n
t (m
A
)
Operating
Region