Figure 5-7: Ethernet/IP Communications Page
Table 5-3: System Settings>Protocols>EtherNet/IP
Terms
Description
Assembly Object
Type
Ethernet/IP use Static assembly object.
Ethernet/IP TCP
Port
The TCP Port used to access Ethernet/IP TCP data directly from the Gateway.
Ethernet/IP UDP
Ports
The UDP Ports used to access Ethernet/IP UDP data directly from the Gateway.
Incorporate
value’s associated
status as error?
If the HART variable status indicates a critical failure or if there is a loss of
communications, it will be reported through the Ethernet/IP member.
Value reported for
error (floating
point)
Chooses what value is reported if the value’s associated status indicates a
critical failure. Only used if the Gateway is using float representation
NaN
Not a number is reported if the value’s associated status indicates a critical
failure.
+Inf
Positive infinity is reported if the value’s associated status indicates a critical
failure.
-Inf
Negative infinity is reported if the value’s associated status indicates a critical
failure.
Other
User defined value is reported if the value’s associated status indicates a
critical failure.
Operation and Maintenance
Reference Manual
September 2020
00809-0200-4420
54
Emerson.com/Rosemount
Summary of Contents for Smart Wireless Gateway 1420
Page 1: ...Reference Manual 00809 0200 4420 Rev HE September 2020 Emerson Wireless 1420 Gateway ...
Page 34: ...Installation Reference Manual September 2020 00809 0200 4420 34 Emerson com Rosemount ...
Page 42: ...Commissioning Reference Manual September 2020 00809 0200 4420 42 Emerson com Rosemount ...
Page 62: ...Troubleshooting Reference Manual September 2020 00809 0200 4420 62 Emerson com Rosemount ...
Page 84: ...DeltaV Ready Reference Manual September 2020 00809 0200 4420 84 Emerson com Rosemount ...
Page 95: ...Reference Manual 00809 0200 4420 September 2020 Emerson com Rosemount 95 ...