Table 5-3. Setup>EtherNet/IP>EtherNet/IP Communication
Unmapped parameter read response?: This is the value returned by the Gateway if the
EtherNet/IP master requests a register with no data assigned to it (empty register). It is
recommended this be set to zero fill to prevent errors.
Parameter mapping
Register Mapping is the process of assigning data points from wireless field devices to
EtherNet/IP registers. These registers can then be read by a EtherNet/IP master or client.
EtherNet/IP register mapping can be found by navigating to Setup>EtherNet/IP>Mapping.
Terms
Description
Assembly Object Type
EtherNet/IP use Static assembly object.
EtherNet/IP TCP Port
The TCP Port used to access EtherNet/IP TCP data directly
from the Gateway.
EtherNet/IP UDP Ports
The UDP Ports used to access EtherNet/IP UDP data
directly from the Gateway.
Incorporate value’s
associated status as
error?
If the HART variable status indicates a critical failure or if
there is a loss of communications, it will be reported
through the EtherNet/IP member.
Value reported for error
(floating point)
Chooses what value is reported if the value’s associated
status indicates a critical failure. Only used if the Gateway
is using float representation
NaN
Not a number is reported if the value’s associated status
indicates a critical failure.
+Inf
Positive infinity is reported if the value’s associated status
indicates a critical failure.
-Inf
Negative infinity is reported if the value’s associated
status indicates a critical failure.
Other
User defined value is reported if the value’s associated
status indicates a critical failure.
Value reported for error
(native integer)
User defined value is reported if the value’s associated
status indicates a critical failure. Only used if the Gateway
is using integer representation.
Summary of Contents for Smart Wireless Gateway
Page 1: ...Reference Manual 00809 0200 4420 Rev GA April 2013 Smart Wireless Gateway ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0200 4420 Rev GA Title Page April 2013 ...
Page 8: ...4 Reference Manual 00809 0200 4420 Rev GA Table of Contents April 2013 Table of Contents ...
Page 80: ...72 Reference Manual 00809 0200 4420 Rev GA Appendix C DeltaV ready April 2013 ...
Page 90: ...82 Reference Manual 00809 0200 4420 Rev GA Appendix D Redundancy April 2013 ...
Page 91: ......