68 Chapter 6 Web Page Of MSC-C
SmartCabinet Integrated Solution User Manual
Note
If the SMS Modem is connected through USB port, you need to modify the jumper locations by referring to Table 3-7.
z
RDU Voice Notification System Setting
1) Type the server IP address in the
Server IP
field;
2) Type the port number in the
Port
field, and the default is 13393;
3) Select whether to
Receive Alarm Restore msg
;
4) Click the
Save
button to save the voice notification system setting.
z
Email Server Configuration
1) Type the server IP address or domain name in the
Email Server
field;
2) Type the
Server Port
,
Email User
,
Email Password
and
Sender Email Address
in the corresponding fields;
3) Click the
Save
button to save the configuration of current user
’
s Email server.
4) Click the
Default
button to restore default setting.
Note
1. The
Server Port
is 25 by default. When SSL is chosen, the
Server Port
will become 465 automatically;
2. The
Email User
is RDU-A by default;
3. When using SSL, you need to ensure that the Email server supports SSL function.
3. Scheduled Notification Configuration
Click the
Alarm Notification
submenu under the
Alarm Management
menu, and then click the
Scheduled
Notification Configuration
tab, the page shown in Figure 6-31 pops up.
Figure 6-31 Scheduled notification configuration
Note
1. Scheduled notification configuration must be used together with alarm notification configuration; otherwise, you cannot select
User Name
,
Notification by
and
Language type
;
2. For scheduled notification configuration, the notification method
‘
Phone
’
is not supported;
3. The scheduled notification means sending the running state of the MSC-C system (normal or alarm) to the user.
1) First of all, on the
Alarm Notification Configuration
page, complete and save the setting of
User
,
Notification
by
and
Language type
.
2) On the
Scheduled Notification Configuration
page, set the
Notification Enabled Period
(setting range: 8:00 ~
20:00),
Notification Scheduled Cycle
(default: Hour),
Interval of Notification
(default: 1) and
Send Time Setting
(default: start time).
3) Click the
Save
button to save the system notification configuration.