Chapter 6 Web Page Of MSC-C 69
SmartCabinet Integrated Solution User Manual
Alarm Actions
Click the
Alarm Actions
submenu under the
Alarm Management
menu to obtain the alarm linkage function, the
page shown in Figure 6-32 pops up.
Figure 6-32 Alarm linkage configuration 1
z
Linkage function
As shown in Figure 6-32, the
Key to Operator/Symbol
list shows all the commands and their usages. Click the
Add
button to add new alarm linkage expression, as shown in Figure 6-33.
Figure 6-33 Alarm linkage configuration 2
Firstly select a command, for instance,
‘
OR
’
. In this case, the expression is
‘
signal 1 [Input1 Register] OR signal 2
[Input2 Register] = signal 3 [Output Register]
’
.
Secondly, when
Signal
is chosen for the input and output parameters, first choose the equip name from the
drop-down lists of
Equip/Register
; then choose the signal type from the drop-down lists of
Signal Type
; at last
choose the signal name from the drop-down lists of
Signal Name
; signal 1, 2, 3 can be any available signals of the
MSC-C.
Thirdly, when
Register
is chosen for the parameters, users need to type the register name in the textbox of the
register, for instance, R(0), R(1) and so on, as shown in Figure 6-34.