Chapter 7 Maintenance 87
SmartCabinet Integrated Solution User Manual
Chapter 7 Maintenance
This chapter expounds the maintenance of SmartCabinet, including safety instructions, maintenance of the main
components, disassembly and troubleshooting.
7.1 Safety Instructions
Warning
1. Switch off the power input during the equipment maintenance. Switch off the equipment power unless the testing device needs
power.
2. Only authorized professional technicians are allowed to maintain the system.
1. All maintenance and operation must follow the local laws, especially the regulations about the electric power,
refrigeration and production.
2. Comply with the manufacturer instructions during maintenance. Failure to observe this could result in invalidation
of warranty.
3. Ignoring the safety instructions will endanger personnel safety and environment.
4. Unsuitable components will lead to performance decrease or equipment shutdown, it is commended to use the
components made by Emerson.
7.2 Maintenance Of The Main Components
Note
Regular maintenance & inspection are necessary to ensure proper operation of the equipment.
7.2.1 MSC-C Maintenance
Restoring default setting
Restoring default setting can be finished through two modes: software or hardware.
For software restoring, refer to
Restore System
in
6.4.6 System Options
.
Hardware restoring includes restoring MSC-C admin password (default username: admin, password: emerson) and
MSC-C IP address (default IP address: 192.168.0.252). You can short pin2 and pin3 of jumper J18 on the MSC-C
card to complete hardware restoring. The jumper position is shown in Figure 7-1.
J18 jumper position
Figure 7-1 Jumper position for MSC-C hardware restoring