7.5 GREEN MODE
(continued)
UPSMON Software
: If UPS is connected to a computer with UPSMON software running, the user can change the Green
Mode setting. On the UPSMON software screen, “UPS Control Panel” (see
Figure 7
below), you can to enable and disable
Green Mode Control by clicking the appropriate box highlighted in the figure.
Figure 7: UPS Control Panel, Configuration
7.6 STANDBY MODE
This feature is only available during back-up mode. Standby mode can be executed remotely using the
COMM CARDs. This feature puts the UPS on standby in 3 minutes and auto-recovers once AC power returns.
This 3 minute window (or maximum run time depending on loading) allows the user to shut off or place
equipment into safe mode.
7.7 REMOTE ON/OFF
•
Allows the user to perform remote power ON/OFF functions using a switch on terminals
(non-polarized) to toggle ON/OFF state.
•
To Enable the UPS, close the switch that is connected to the terminals.
•
To Disable the UPS, open the switch that is connected to the terminals.
Remote Enable/Disable of UPS
SDU-A Remote
ON/OFF Switch Wired
UPS Condition/State
Switch or Terminal Condition
UPS-A
ON
UPS-A
OFF
Remote ON/OFF Terminals : Shorted (closed) for ON, Open for OFF Non-Polarized terminals.
No external voltage is required. We recommend using stranded UTP (Unshielded Twisted Pair)
wire for connections.