background image

 

 

 

 
 

 

Uninterruptible  Power Supply 
User Manual

 

 
 
 
 
 
 
 
 

 

 

 

SDU AC B-Series 

 

 
 
 
 
 
 
 
 

 

 

Summary of Contents for SolaHD SDU 500B

Page 1: ...Uninterruptible Power Supply User Manual SDU AC B Series ...

Page 2: ...4 3 0 GeneralDescription Page 5 4 0 System Block Diagram Page 7 5 0 Installation Instruction Page 8 6 0 Operation Instruction Page 10 7 0 LEDDiagnostics Page 11 8 0 Battery Replacement Page 12 9 0 Troubleshooting Page 14 10 0 Technical Specifications Page 15 11 0 Software Interface Page 17 TechnicalSupport Page 18 Warranty Page 18 ...

Page 3: ... the wall back of the panel or enclosure Please contact Tech Supportfor details SDUEDC Side Mount Enhanced DIN Rail Clip SDUCFRELAYCARD Dry contactrelay status with LED diagnostics and standby Mode capability Please refer to SDU B Series COMM Cards Manual Active IndustrialEthernet Cards Network communication module is a high performance communication solution for industrial field devices It is des...

Page 4: ...e battery Auto restart during AC recovery AC overload protection Over temperature thermal protection Battery overcharge protection Input voltage out of range protection Remote monitoring and control software via UPSwatch Power lock feature ensuring the UPS must be connected to utility on initial startup after unboxing Pass through feature where the UPS can power the load with AC in event of batter...

Page 5: ...ransition to Back Up Mode Due to Power Outage Input voltage range is 75 to 120 ideal protection for the critical connected loads Battery charging occurs automatically when AC power is applied no need to switch ON the UPS The SDU also includes an automatic self test feature to test the UPS function and battery UPSWatch will record the event on EVENT LOG UPS immediately switches to AC Mode to provid...

Page 6: ...htor close to heat emitting sources To allow proper ventilation of the UPS do notblock or cover the top and bottom sides of the unit Do not insert any objects into the ventilation holes or other openings of the UPS Keep all vents free of dust accumulation that could restrict airflow Do not dispose of batteries in a fire they may explode Do notopen or damagethe battery Released electrolyte is harmfu...

Page 7: ...e button for less than one second to activate the self testing After self test24 hours is needed before another self testcan be performed to avoid battery degradation Monthly automated self testprogramed by default 2 Battery Warning Overload Indicator Red LED The LEDflasheswhenthebatteryneedsto berechargedandtested The LED will illuminate whenthe unitis subjected to an overload condition If the uni...

Page 8: ...WerecommendusingstrandedUTP UnshieldedTwistedPair wirefor connections Remote ON OFF is grounded to the UPS internal signal ground so it should be isolated from the chassis ground to prevent any ground potentials that may cause a unit malfunction or damage In addition isolate the Remote ON OFF wiring away from high current high voltage and high frequency components to prevent any magnetically coupl...

Page 9: ...v 12 2021 7 P a g e 4 0 System Block Diagram L N E L N E BRIDGE RECTFITER RECTFITER AC TO DC DC BOOSTED TO HIGH DC LEVEL DC TO STEP SINE WAVE AC UPS OUTPUT RELEY FILTER INPUT FUSE Figure 4 SDU AC B Series UPS SystemBlock Diagram ...

Page 10: ...tdoors Itis required that an input breaker is added in front of the UPS COMMCARDInstallation To install the optional card remove the COMM PORT cover and insert the card Refer to the SDU COMM CARD Manual for more details Refer to inside cover for COMM CARD options or contactyour SolaHD representative DIN Rail Mounting Followinstructions below Figure6 Mounting theUPS DIN Rail A Tilt unit as illustra...

Page 11: ...ne in neutral supply conductors Connect the loads to the output hardwire connector Verify proper wiring connections then apply power to the UPS Reference Figure2 Wire Gauge 8 18 AWG Screw Torque 9lb in 101 7N cm InternalBattery Charge the UPS battery for a minimum of 8 hours before initial use The UPS charges its battery whether the UPS is on or off whenit is connected to AC power WarningLabel App...

Page 12: ... verifies both the operation of the UPS and the condition of the battery In AC mode press and release the POWER ON OFF TEST button for 1 second to perform a self test During the self test the UPS momentarily operates in back up mode YELLOW LED will illuminate for 10 seconds then will change back to GREEN If the UPS passes the self test it returns to AC mode In AC mode for 30 Days the UPS will auto...

Page 13: ...forON Open forOFF Non Polarizedterminals No externalvoltageis required We recommendusing stranded UTP Unshielded TwistedPair wire for connections 7 0 LED Diagnostics Condition Description LED Alarm BACK UP MODE UPSis in back up mode due to AC Loss YELLOW Slow beeping UPSsoundsuntil AC utility power recovers AC MODE Normal conditionsource suppliedbyAC Mains GREEN No Alarm AC MODE OVERLOAD Loadaroun...

Page 14: ...pe XTV1285F2FR Yuasa REW45 12FR Step 1 Remove battery cover Step 2 Disconnect the terminal of battery wire Figure7 Disconnect the BatteryWire and Remove Cove The battery may be replaced by service personnel only When the UPS is installed in a Class I Division 2 Groups A B C D or Class I Zone 2 II C hazardous location adhere to the following Warning Explosion Hazard Do notconnect or disconnect the ...

Page 15: ...SDU AC B Series A272 353 Rev 12 2021 13 P a g e Step 3 Take out the battery Figure8 Take out the Battery Notice Battery replacement distance required L 250mm Figure9 Batteryreplacement space ...

Page 16: ...e Power Lock feature is disabled Battery is defective Replace the battery UPS fault Contact Tech support The UPS is always on battery mode Input may not be properly connected Check the input connection Input fuse is open Before reconnecting equipment please verify that the load matches the UPS capability specified and output has short circuit protection Contact Tech support Actual backup time cann...

Page 17: ... or battery defect BATTERY Type Sealed maintenance free lead acid batteries Typical Recharge Time 8hours Typical Back Up Time at full load 4 20min 1 30min 4 20min 1 30min ALARM ON Battery Slow beepingevery10seconds Battery Low Rapidbeepingeverysecond Overload Continuousbeeping sound ENVIRONMENT Ambient Operation 0 95 humidity non condensing OrdinaryLocation 0 50 C up to 3000m HazardousLocation 0 4...

Page 18: ...FR Yuasa REW45 12FR Load Level Approximate Back Up Time Minutes Approximate Back Up Time Minutes 50 14 30 14 30 7 00 7 00 100 4 20 4 20 1 30 1 30 Table2 BatteryBack Up Time Chart Note Run times in this table are approximate They are based upon new fully charged standard battery modules at a temperature of 25 C 77 F with 100 resistive UPS loading Run times listed above can vary due to manufacturing...

Page 19: ...ows 2008 2012 Server Core Hyper V 2008 2012 Oracle Linux 7 1 Linux OpenSUSE 11 4 Linux Ubuntu 10 04 Linux Fedora 3 1 9 CentOS 5 8 Citrix XenServer 6 0 0 and Linux KVM Figure10 Connecting UPS toComputer With the UPSWATCH software users can perform monitoring functions and an orderly shutdown of protected equipmentin the eventof power failure UPSWATCH displaysdiagnostic information such as voltage f...

Page 20: ...ons are subjectto change withoutnotice Contact Information Website www solahd com Technical Services E Mail solahd technicalservices emerson com Warranty Please see the Terms Conditions of Sale While every precaution has been takento ensure accuracy and completeness in this manual Appleton Grp LLC d b a Appleton Groupassumes no responsibility and disclaims all liability for damages resulting from ...

Page 21: ...striel Nord 35 rueAndréDurouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 22541390 China Sales Office Shanghai T 86 21 33387000 Canada EGS Electrical Group Canada Ltd 99Union Street ElmiraON N3B3L7 Canada T 1 8887652226 Middle East Sales Office Dammam Saudi Arabia T 966 135103702 Asia Pacific EGS Private Ltd Block 4008 Ang Mo Kio Ave 10 04 16TechPlace1 Singapore569625 T 65 65561100 Chile Sales ...

Reviews: