Uninterruptible Power Systems 

Instruction Manual

SDU AC - A SERIES COMM CARDS

Active Card

Passive Card

Summary of Contents for SolaHD SDUECATCARD

Page 1: ...Uninterruptible Power Systems Instruction Manual SDU AC A SERIES COMM CARDS Active Card Passive Card ...

Page 2: ... 1 Identifiction 9 4 0 Interface and Mechanical Description 12 4 1 SDU COMM CARD Interface To UPS 12 4 2 SDU COMM CARD Interface To End User Network 13 4 2 1 SDUENETIPCARD Connectors for Network Interface 13 4 2 2 SDUCFRELAYCARD Interface 13 5 0 Specifications 15 6 0 Data Exchange 16 6 1 Network Data Access 16 6 2 Process Data Exchange 18 6 3 Web Server 19 7 0 Operating and Storage Temperature 20 ...

Page 3: ...2 Figure 11 RJ45 Connector For Ethernet Style Card 13 Figure 12 SDUCFRELAYCARD Front Face 13 Figure 13 SDUCFRELAYCARD PIN Standby Circuit 14 Figure 14 Web Server Window Example 19 TABLES Table 1 LED Status for SDUENETIPCARD 5 Table 2 LED Status for SDUECATCARD 6 Table 3 Ethernet Interface RJ45 Connectors for SDUECATCARD 6 Table 4 LED Status for SDUMBUSCARD 7 Table 5 LED Status for SDUPNETCARD 8 Ta...

Page 4: ...u omisión 2018 SolaHD Todos los derechos reservados en el mundo entero Las especificaciones pueden cambiar sin previo aviso EtherNet IP is a registered trademark of ODVA www odva org El nombre y el logotipo de SolaHD son marcas registradas de Appleton Grp LLC d b a Appleton Group Todos los nombre mencionados son marcas comerciales o registradas de sus respectivos titulares Bien que toutes les préc...

Page 5: ...rom the following website www odva org 1 1 2 Other Industrial Protocols Modules to supports fast Industrial Internet communication speeds with other networks are being developed Contact your SolaHD representative for availability SDUMBUSCARD Modbus TCP 2 port COMM CARD which enables your products to communicate on an Modbus TCP network SDUPNETCARD Profinet IRT 2 port COMM CARD which enables your p...

Page 6: ... refer to the SolaHD YouTube video https youtu be 1wYElxdjL50 1 2 3 TORX 8 0 25Nm Card hook SDU COMM CARD CompactFlash 1 When securing the module into the SDU ensure that the card module is properly aligned into the CompactFlash socket inside the UPS prior to applying any force The card hook should be aligned with the PCB 1 2 3 TORX 8 0 25Nm 1 2 3 TORX 8 0 25Nm 2 Turn the screws in a clockwise dir...

Page 7: ...round spring pin on the bottom of the card to the PCB in the port Insert the COMM CARD into the compact flash connector until it is properly seated to the connector and PCB when flush with the front surface of the UPS After the card is properly seated positioned tighten down the card screws to properly secure the card Figure 2 Installing Communication Card to UPS Special Instruction Ground PIN SDU...

Page 8: ...ork Processor On board DC DC converter opto couplers and physical layer Status LEDs x2 Tightening screws x2 Integrated shield connections underside Network specific connector Robust plastic housing Figure 3 SDUENETIPCARD Construction 4 3 0 System Features and General Description ...

Page 9: ...licate IP address FATAL error Red flashing One or more connections timed out CIP Class 1 or 3 Module Status LED Off No power Green Controlled by a Scanner in Run state Green flashing Not configured or Scanner in Idle state Red Major fault EXCEPTION state FATAL error etc Red flashing Recoverable fault s Module is configured but stored parameters differ from currently used parameters LINK Activity L...

Page 10: ...Red single flash Unsolicited state change Slave device application has changed the EtherCAT state autonomously Red double flash Sync Manager watchdog timeout Watchdog Functionality Red Application controller failure If RUN and ERR turn red this indicates a fatal event forcing the bus interface to a physically passive state Flickering Booting error detected E g due to firmware download failure LINK...

Page 11: ... message Red IP address conflict detected FATAL ERROR Red flashing Connection timeout No Modbus message has been received within the configured process active timeout time Module Status LED Off No power Green Normal operation Red Major fault FATAL Red flashing Minor fault Alternating red green Firmware update from file system in progress LINK Activity LED 3 4 Off No link no activity Green Link 100...

Page 12: ...r Expected Identification differs from Real Identification Module Status LED Off Not Initialized No power OR Module in SETUP or NW_INIT state Green Normal Operation Module has shifted from the NW_INIT state Green 1 flash Diagnostic Event s Diagnostic event s present Red Exception error Device in state EXCEPTION Fatal event Major internal error this indication is combined with a red net work status...

Page 13: ... from ETG UINT32 0x00000906 2 Product Code UINT32 1F4 3 Major Rev UINT16 1 4 Minor Rev UINT16 03 5 Serial Number UINT32 Respond with Error 6 MFG Device Name Array of CHAR max 64 SDU Industrial UPS PROFINET SDUPNETCARD object 0xF6 1 Device ID UINT16 1F4 2 Vendor ID from PNO UINT16 Respond with Error 3 Station Type Array of CHAR SDU Industrial UPS 8 I M Order Array of CHAR SDU Industrial UPS 9 I M S...

Page 14: ...S 7 8 enable remote signaling and allow the UPS to go on STANDBY mode during BACK UP MODE only When in STANDBY MODE the UPS begins a 3 minute counter maximum or set by user in UPSMON that starts once STANDBY MODE is activated by a momentary normally open switch or signal minimum 1 second before UPS will enter STANDBY mode 3 A Bi Color LED to represent UPS condition 10 3 0 System Features and Gener...

Page 15: ...n 1 2 Pin 2 3 Pin 4 5 Pin 5 6 No Fault GREEN GREEN x x AC Fault UPS is on Back Up Mode T RED GREEN x x on Back Up Mode Battery is Low T T RED RED x x Standby Inverter is OFF T OFF OFF x x Table 8 SDUCFRELAYCARD Relay Logic and LED State Figure 9 SDUCFRELAYCARD Application Block Diagram SDU AC A Series comm cards instruction Manual 11 ...

Page 16: ...nector that is designed to simplify the mounting and to meet the demands for a secure and stable connection of the communication modules Figure 10 SDU COMM CARD Interface to UPS NOTICE UPS should be turned OFF powered down when COMM CARD modules are installed or removed Failure to observe this practice may cause damage to the UPS or to the COMM CARD 12 4 0 Interface and Mechanical Description ...

Page 17: ... style connector Push the plastic pin and insert the wire into the hole then release to lock it in place Each terminal position can accommodate 0 2 1 5 mm2 AWG 24 AWG 16 wire The maximum force that should be applied on the connector mechanism is 40 N 9lbs The CF RELAY CARD is design for Safety Extra Low Voltage SELV circuit applications only Figure 12 SDUCFRELAYCARD Front Face Pin 1 BLUE SDU AC A ...

Page 18: ...e maximum current on the relay contact side is 1A limited by the allowable trace width The STANDBY input is shown by the schematic The TX signal going to UPS is normally HIGH unless UPS goes to BACK UP Mode and the STANDBY switch is pressed minimum of 2 seconds It requires a momentary N O type switch to be connected on PINS 7 and 8 Upon pressing the external switch or simulating closure of pins 7 ...

Page 19: ...lution Degree 3 UL 508 Pollution Degree 3 CSA 107 1 EU ROHS2 China ROHS2 Temperature F C Storage 40 to 185 40 to 85 Operating 40 to 158 40 to 70 Convection cooling no forced air required Vibration Operating IEC60068 2 6 Sine Wave 10Hz to 500Hz 19 6m S displacement of 0 35mm 60 min per axis for all X Y Z direction Non Operating IEC60068 2 6 Random 5hz to 500Hz 2 09Grms 20 min per axis for all X Y Z...

Page 20: ...ocess Data BYTE2 3 108 UINT 16 Output Vol V 09 Get access Write Process Data BYTE4 5 109 UINT 8 Input Freq Hz 09 Get access Write Process Data BYTE6 110 UINT 8 Output Freq Hz 09 Get access Write Process Data BYTE7 111 UINT 8 UPS Status 1 09 Get access Write Process Data BYTE8 112 UINT 8 UPS Status 2 09 Get access Write Process Data BYTE9 113 UINT 8 Model Num 09 Get access Write Process Data BYTE10...

Page 21: ... 111 UPS Status 1 bit 0 is line fail 1 INV 0 LINE bit 1 is low battery 1 BAT LOW 0 NORMAL bit 2 reserved bit 3 reserved bit 4 reserved bit 5 LOAD STATUS 1 OVER LOAD 0 NORMAL bit 6 reserved bit 7 SD MODE DISPLAY ADI Inst 112 UPS Status 2 bit 0 reserved bit 1 BAT STATUS 1 BAD 0 NORAML bit 2 TEST MODE 1 TEST 0 NORMAL bit 3 Buzzer Silence on off 1 Silence Buzzer silence off Alarm Enabled Buzzer silenc...

Page 22: ...Time MIN 0 60 B IS Schedule Off Time SEC 0 59 ADI Inst Instance number of the Host Application Data Object DataType Data type e g UINT8 Name Variable Name available on some networks Get SET is the value GET able from the network Process Data Exchange variable able to be mapped to process data exchange Range Min minimum value for SET access For range checking of inputs Range Max maximum value for S...

Page 23: ...bit 6 DISBLE NO LOAD SHUTDOWN 1 ACTIVE bit 7 reserved BYTE10 UPS model number 32H 500VA 120V 39H 500VA 230V 52H 850VA 120V 59H 850VA 230V BYTE11 UPS PRE SD COUNT TIME MIN BYTE12 UPS PRE SD COUNT TIME SEC BYTE13 14 UPS PRE ON COUNT TIME BYTE15 UPS FIRMWARE Ver Output 8 Bytes The command Instance is mapped to output message structure is the same as outlined in the command instance chapter 6 3 Web Se...

Page 24: ...al SolaHD no asume responsabilidad alguna y rechaza toda responsabilidad por daños que pudieran resultar debido al uso de esta información o por cualquier error u omisión 2018 SolaHD Todos los derechos reservados en el mundo entero Las especificaciones pueden cambiar sin previo aviso EtherNet IP is a registered trademark of ODVA www odva org El nombre y el logotipo de SolaHD son marcas registradas...

Page 25: ...struction materials group has the products to meet your needs Power Quality Solutions The SolaHD brand offers the broadest power quality line including uninterruptible power supplies power conditioners voltage regulators shielded transformers surge protection devices and power supplies Heating Cable Systems This group is made up of the EasyHeat and Nelson brands They offer a broad range of electri...