background image

Page: 5

4.0 System Block Diagrams

SLN System Block Diagram

SPS System Block Diagram

Summary of Contents for SolaHD SLN Series

Page 1: ...Uninterruptible Power Supply User Manual SPS and SLN UPS Series ...

Page 2: ... Introduction 1 2 0 Important Safety Instructions 2 3 0 General Description 3 4 0 System Block Diagrams 5 5 0 Installation and Operation 6 6 0 LED Diagnostics 7 7 0 Troubleshooting 8 8 0 Technical Specifications 9 ...

Page 3: ...ppleton and Emerson logos are registered in the U S Patent and Trademark Office All other product or service names are the property of their registered owners 5 Secure the top of the bracket with the two 2 remaining screws Figure 2 6 Tighten all four 4 screws Make sure the bracket and UPS are secure Figure 3 Technical Support Phone 800 377 4384 option 2 E mail solahd technicalservices emerson com ...

Page 4: ...connect the input power supply cord from the AC power outlet Connect the AC input power cord to a properly grounded AC supply source Connect the UPS to a grounded supply circuit with proper branch circuit protection Follow all applicable National Electrical Codes NEC and Canadian Electrical Codes CEC as well as all local codes Do not plug the UPS into a power strip Do not daisy chain one UPS power...

Page 5: ...tch Red LED Indicator Green LED Indicator When the Green LED Indicator Shows a steady light the UPS is in AC Mode Is flashing the UPS is in Battery Mode For more details refer to Section 6 0 LED Diagnostics 3 2 Back Panel Models SLN600 SPS850 Breaker AC Input Cord USB B TYPE Output Receptacles ...

Page 6: ...Page 4 3 3 Back Panel Model SLN1000 Breaker AC Input Cord USB B TYPE Output Receptacles 3 4 Back Panel Model SLN1500 Output Receptacles Breaker AC Input Cord USB B TYPE ...

Page 7: ...Page 5 4 0 System Block Diagrams SLN System Block Diagram SPS System Block Diagram ...

Page 8: ...ng the UPS To turn on off the UPS press the power switch for 3 seconds When the Green LED Indicator Shows a steady light the UPS is in AC Mode Is flashing the UPS is in Battery Mode 5 4 Battery Charging Plug AC input cord into utility power for at least eight 8 hours in order to fully charge the battery prior to use as some charge may have been lost during shipping Unit does not need to be turned ...

Page 9: ...ng every 1 second OFF OFF Standby Mode OFF ON Continuous beep every 1 minute for 1 hour Fault Alarm OFF Flashing every 10 seconds 1 beep every 10 seconds Over Temperature Flashing every 10 seconds OFF OFF Charging OFF Flashing every 3 seconds Continuous beep every 3 seconds until fault is removed Output Short Flashing every 3 seconds OFF OFF Automatic Voltage Regulation AVR Mode SLN Model Only NOT...

Page 10: ...s been operating at high temperatures that are not conducive to the battery If the battery is near the end of its life please contact Customer Support Charger fault or other reasons Contact Tech Support The red LED is on and beeps The UPS has overloaded Please disconnect loads or check if the load is shorted or malfunctioning Green LED flashes every 1 second with no sound and no output voltage Bat...

Page 11: ...min 26 sec 50 13 min 30 sec 9 min 6 sec 13 min 10 min 9 sec 60 10 min 30 sec 6 min 40 sec 10 min 30 sec 8 min 11 sec 70 8 min 10 sec 5 min 6 sec 8 min 6 min 22 sec 80 6 min 30 sec 4 min 7 sec 5 min 50 sec 5 min 13 sec 90 4 min 40 sec 3 min 5 sec 4 min 4 min 6 sec 100 3 min 28 sec 2 min 20 sec 3 min 2 min 55 sec NOTE Run times in this table are approximate They are based upon new fully charged stan...

Page 12: ... 85 at Buck mode N A Vout Input 102 Vac x 118 at Boost mode Vout Input 138 Vac x 85 at Buck mode Overload Protection Line Mode 1 110 5 load for 5 mins After the power will not be provided to the load Then every 10 mins auto recovery will be attempted 2 120 5 load for 10 seconds After the power will not be provided to the load Then every 10 mins auto recovery will be attempted 3 130 5 load for 1 5 ...

Page 13: ...The Output current continues over 125 within 60ms to OSCP and then goes to Battery MODE 2 UPS goes to retry mode every 10 seconds until the Battery Voltage VB 11V cell 3 The Battery recharges when the VB 12 7V cell then UPS continues retry mode every 10 seconds 4 UPS goes to auto recovery mode until the short circuit disappears then goes back to LINE Mode Battery Parameters Battery Type VRLA maint...

Page 14: ...rt Website www solahd com Technical Support E Mail solahd technicalservices emerson com Toll Free 800 377 4384 USA 847 268 6651 Warranty Please see the Terms Conditions of Sale document within the UPS packaging While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Grp LLC d b a Appleton Group assumes no responsibility and disclaims all liability for dama...

Page 15: ...ce Industriel Nord 35 rue André Durouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 2254 1390 China Sales Office Shanghai T 86 21 3338 7000 Canada EGS Electrical Group Canada Ltd 99 Union Street Elmira ON N3B 3L7 Canada T 1 888 765 2226 Middle East Sales Office Dammam Saudi Arabia T 966 13 510 3702 Chile Sales Office Las Condes T 56 2928 4819 India Sales Office Chennai T 91 44 3919 7300 Korea Sa...

Reviews: