Table 9-4 Menu 4 Regen parameter descriptions
This parameter is the r.m.s. input current to the drive. The phase currents consist of an active component and a reactive component. The three phase
currents can be combined to form a resultant current vector as shown below:
The resultant current magnitude is displayed by this parameter. The active current is the torque producing current for a motor drive and the real
current for a Regen drive. The reactive current is the magnetising or flux producing current for a motor drive.
The active current is the real current in a Regen drive.
The active current is aligned with the y axis of the reference frame. The y axis of the reference frame is aligned with the Regen drive terminal voltage
vector.
Parameter
Range(
Ú
)
Default(
Ö
)
Type
4.01
Current magnitude
0 to DRIVE_CURRENT_MAX A
RO Uni FI NC PT
4.02
Active current
±DRIVE_CURRENT_MAX A
RO Bi
FI NC PT
4.04
Current demand
±TORQUE_PROD_CURRENT_MAX %
RO Uni FI NC PT
4.05
4.06
4.07
Symmetrical current limit
0 to MOTOR1_CURRENT_LIMIT_MAX %
175.0
RW Uni
4.08
Reactive current reference
±REGEN_REACTIVE_MAX %
0.0
RW Bi
US
4.13
Current controller Kp gain
0 to 30,000
90
RW Uni
US
4.14
Current controller Ki gain
0 to 30,000
2,000
RW Uni
US
4.15
Thermal time constant
0.0 to 400.0
89.0
RW Uni
US
4.16
Thermal protection mode
0 to 1
0
RW Uni
US
4.17
Reactive current
±DRIVE_CURRENT_MAX A
RO Bi
FI NC PT
4.18
Overriding current limit
0 to TORQUE_PROD_CURRENT_MAX %
RO Uni
NC PT
4.19
Overload accumulator
0 to 100.0 %
RO Uni
NC PT
4.20
Percentage load
±USER_CURRENT_MAX %
RO Bi
FI NC PT
4.24
User current maximum scaling
0.0 to TORQUE_PROD_CURRENT_MAX %
175.0
RW Uni
US
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not cloned
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
4.01
Current magnitude
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
2
1
1
1
1
Range
Regen
0 to DRIVE_CURRENT_MAX A
Update rate
4ms
4.02
Active current
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
2
1
1
1
Range
Regen
±DRIVE_CURRENT_MAX A
Update rate
4ms
Direction of active current
Power flow
+
From supply
-
Into supply
Pr
4.02
Resultant
output current
Pr
4.01
Pr
4.17